Parameter Assignment - Siemens SIMATIC RQ 4x120VDC-230VAC/5A CO HA Manual

Digital output module for et 200sp ha
Table of Contents

Advertisement

A.2

Parameter assignment

Parameter assignment in the user program
You can reconfigure individual channels of the module in RUN without this having an effect
on the other channels.
Changing parameters in RUN
The "WRREC" instruction is used to transfer the parameters to the module using data
record 128. The parameters set in STEP 7 are not changed in the CPU, which means that the
parameters set in STEP 7 will be valid again after a restart.
Output parameter STATUS
If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
● Byte1: Function_Num, general error code
● Byte2: Error_Decode, location of the error code
● Byte3: Error_Code_1, error code
● Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 /
Error_Code_2.
Error_
Error_
Cause
Code_
Code_
1
2
0xB0
0x00
Number of the data record unknown
0xB1
0x01
Length of the data record is incorrect
0xB2
Varia‐
Module cannot be reached
ble
0xE0
0x01
Wrong version in the header
0xE0
0x02
Header error (number or length of parameter block)
0xE1
0x01
Reserved bit set
0xE1
0x06
Invalid encoding for substitute value reaction
Valid parameters
Only the values specified in the following are permitted. Values that are not listed are rejected
by the module.
Digital Output Module RQ 4x120VDC-230VAC/5A CO HA (6DL1132-6HD50-0PK0)
Manual, 11/2017, A5E39389042-AC
Drivers, parameters, diagnostics messages and address space
[ID: 80188477835]
Solution
Enter valid number for data record.
Enter valid value for data record length.
● Check station - is the module plugged in
correctly?
● Check the parameters of the WRREC
instruction.
Correct the version number of the parameter block.
Correct the length and number of the parameter
blocks.
Check and correct the parameters
A.2 Parameter assignment
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6dl1132-6hd50-0pk0

Table of Contents