Chapter 3 Functions
3-1 Self-diagnosis Function
This device is equipped with a self-diagnosis function.
The device performs self-diagnosis when the power is supplied and during operation.
If an error is found, lockout occurs at the time and the control outputs 1 / 2 (OSSD 1 / 2) are
fixed to OFF. Refer to "Chapter 5 Troubleshooting" to eliminate the cause of the error.
3-2 Interlock Function
For control output 1 / 2 (OSSD 1 / 2), manual / auto reset in interlock can be selected.
Manual / Auto reset can be selected by the wiring of the reset input terminals (X1, X2, and X3).
Terminal
X1 - X2 connection
X1 - X3 connection
3-2-1 Manual Reset
Even if detecting output of sensor is ON (without liquid leak), control outputs 1 / 2 (OSSD 1 / 2)
cannot be automatically ON.
A reset button and a back check circuit (KA, KB) should be prepared between X1 and X2 to
monitor an external device. If a back check circuit (KA, KB) is not required, only the reset button
should be prepared.
When the sensor is ON, it can be recovered with start-up of the external reset button.
<When back check circuit is required>
<When back check circuit is not required>
Note: The reset will be canceled in case cleaning of sub detection part is not enough or detecting auxiliary out-
put (white) of safety leak sensor is broken.
© Panasonic Industriar Devices SUNX Co., Ltd. 2016
Operation
Manual reset
Auto reset
In using the interlock function, make sure that there is no operator in the danger-
ous zone. Otherwise, death or injury may occur.
X1
Reset button
X1
Reset button
Mount the reset button a place where the entire dangerous zone can always be
known and the button can be operated outside the dangerous zone.
KA
KB
X2
X2
Functions
21