Lockout Cancel Function - Panasonic SQ4-C11 Instruction Manual

Controller for safety liquid leak sensor sq4-a series
Hide thumbs Also See for SQ4-C11:
Table of Contents

Advertisement

3-5 Auxiliary Output Function (Non-safety Output)
This device is equipped with auxiliary output as non-safety application.
Terminal
No.
ERR
Lockout output
SUB
Auxiliary output
AUX1
Sensor monitoring output 1 Monitor output corresponding to detection auxiliary output of sensor No. 1
AUX2
Sensor monitoring output 2 Monitor output corresponding to detection auxiliary output of sensor No. 2
AUX3
Sensor monitoring output 3 Monitor output corresponding to detection auxiliary output of sensor No. 3
AUX4
Sensor monitoring output 4 Monitor output corresponding to detection auxiliary output of sensor No. 4
<Time chart of lockout output>
Controller
operation
Normal
Lockout output
(ERR)
<Time chart of auxiliary output>
Control output 1 / 2
(OSSD 1 / 2)
Auxiliary output (SUB)
(Negative logic of OSSD)
<Time chart of senosr monitor outputs 1 to 4>
Sub detection of
sensors No.1 to 4
Sensor monitor
output 1 to 4
(AUX1 to 4)

3-6 Lockout Cancel Function

After removing cause of the error, The lockout can be canceled by method listed below.
1) Tuns ON power supply again.
2) Reset operation from reset input terminal.
<Manual reset>
After short circuit between X1 and X2 30ms or more, open again.
<Auto reset>
After open between X1 and X3 30ms or more, short circuit again.
© Panasonic Industriar Devices SUNX Co., Ltd. 2016
Names
OFF for lockout
Negative logic output of control output 1 / 2 (OSSD 1 / 2)
Error
ON
OFF
ON
OFF
ON
OFF
ON
OFF
10ms or less
ON
OFF
Do not use the auxiliary output for the purpose of stopping the machine in which
this device is mounted. Otherwise, death or injury may occur.
Description
100ms or less