Panasonic SQ4-C11 Instruction Manual page 16

Controller for safety liquid leak sensor sq4-a series
Hide thumbs Also See for SQ4-C11:
Table of Contents

Advertisement

Wiring
<Output waveform [Control outputs 1 / 2 (OSSD 1 / 2) are ON]>
When the sensor is ON, the controller self-diagnoses the output circuit.
The output transistor is cyclically OFF. (Refer to the figure below.)
When feedback of the OFF signal is given, the controller evaluates that the output circuit is nor-
mal. If feedback of the OFF signal is not given, the controller evaluates that the output circuit or
wiring has an error and the control outputs 1 / 2 (OSSD 1 / 2) maintains OFF status.
<Time chart>
Control
ON
output 1
OFF
(OSSD 1)
Control
ON
output 2
OFF
(OSSD 2)
16
Perform connection paying attention to the input response time of the unit con-
nected to this device. The unit may malfunction due to OFF signal of this device.
Approx. 2.4ms
Approx. 30 to 60 μs
Approx. 20 μ s
Approx. 30 to 60 μ s
Approx. 30 to 60 μ s
Approx. 20 μ s
© Panasonic Industriar Devices SUNX Co., Ltd. 2016
Approx. 30 to 60 μ s

Advertisement

Table of Contents
loading

Table of Contents