Output; Output 4; Output, Modulating; Output, Multistage - Siemens LMV5 Series Basic Documentation

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Output, modulating

Output, multistage

Siemens Building Technologies
HVAC Products

6.9 Output

6.9.1 Output 4...20 mA
This active output serves primarily for covering the current load, e.g. for boiler
sequence control and for display by the BMS (if no bus interface is used).
If a voltage signal is required, it can be delivered by connecting a resistor (maximum
500 Ohm).
Burner OFF
I (mA)
4
Burner OFF
I (mA)
4
Tolerance ±5 %

6.10 Multiboiler plants

Boiler sequence control is accomplished with the help of external devices or control
systems (e.g. BACS or PCs).
In principle, there are 2 choices available:

6.10.1 Multiboiler plants by means of an analog input

For that purpose, the LC of the LMV5... has an analog input (X62).
This means that the individual boilers can be
a) released / locked, and
b) operated at the required output
(or set to the required setpoint)

6.10.2 Multiboiler plants by means of a digital interface

For that purpose, BACS terminal X72 on the AZL5... can be used with the help of the
bus interface.
Inputs:
Controller release / lock
Predefined setpoint or predefined load
Outputs:
Actual value
Controller ON / OFF
Manipulated variable multistage / modulating
Error messages
For more detailed information, refer to → section 7.2.2 Connection to superposed
systems.
Basic Documentation LMV51...
6 Temperature or pressure controller (internal load controller LC)
0 %
100 %
4
Stage 1
Stage 2
5
10
20
Stage 3
15
85/278
CC1P7550en
01.10.2003