Optimum adaption of the controllers to the controlled system can be checked by
recording the actual value during startup while the controlled system is working. The
diagrams below reveal incorrect settings and give hints on remedy.
Here, the behavior of a controlled system of the 3
The procedure for setting the control parameters can also be applied to other types of
controlled systems.
Practical value for «TN : TV» = 4...6.
XP too small
Tn and Tv too small
x
w
7550d25/0501
Basic Documentation LMV51...
6 Temperature or pressure controller (internal load controller LC)
rd
order for a PID controller is shown.
x
w
t
7550d22/0501
x
w
t
7550d24/0501
Optimum setting
XP too great
Tn and Tv too great
t
CC1P7550en