Checking The Control Parameters; Example - Siemens LMV5 Series Basic Documentation

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Checking the control
parameters

Example

x
w
7550d21/0501
x
w
7550d23/0501
74/278
Siemens Building Technologies
HVAC Products
Optimum adaption of the controllers to the controlled system can be checked by
recording the actual value during startup while the controlled system is working. The
diagrams below reveal incorrect settings and give hints on remedy.
Here, the behavior of a controlled system of the 3
The procedure for setting the control parameters can also be applied to other types of
controlled systems.
Practical value for «TN : TV» = 4...6.
XP too small
Tn and Tv too small
x
w
7550d25/0501
Basic Documentation LMV51...
6 Temperature or pressure controller (internal load controller LC)
rd
order for a PID controller is shown.
x
w
t
7550d22/0501
x
w
t
7550d24/0501
Optimum setting
XP too great
Tn and Tv too great
t
CC1P7550en
01.10.2003
t
t