Siemens LMV5 Series Basic Documentation page 261

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Siemens Building Technologies
HVAC Products
18.8.2
CAN bus X84, X85
The O
module is to be connected to the basic unit via CAN bus. There are 2 terminals
2
for the CAN bus, X84 for the supply and X85 for the connection of the AZL5... If the O2
module is located at the end of the bus line, the CAN bus termination must be
activated.
18.9 Configuration of O2 module
The connected sensors are to be configured via the AZL5...
The O2 sensor connected to terminals X81 / X89-02 must be parameterized.
Parameter:
O2 Sensor (NoSensor, QGO20)
The combustion air temperature sensor connected to terminal X87 must be
parameterized.
Parameter:
Combustion air temperature sensor (NoSensor, Pt1000, LG-
Ni1000)
The flue gas temperature sensor connected to terminal X86 must be parameterized.
Parameter:
Flue gas temperature sensor (NoSensor, Pt1000, LG-Ni1000)
Basic Documentation LMV51...
18 Addendum 4: LMV52... with O2 trim control and O2 module
261/278
CC1P7550en
01.10.2003