15 Addendum 1: List of fault status messages of LMV51... system
Display
Parameter Set damaged
Page has been set to ABORT
Parameter Backup Restore
Page has been set to RESTO
Internal Fault Load Controller
Page has an invalid status
Internal Fault Load Controller
CAN error
Internal Fault Load Controller
CAN error
Internal Fault Load Controller
CAN error
Internal Fault Load Controller
CAN error
Internal Fault Load Controller
CAN error
Short-circuit Pt100 Sensor
Short-circuit sensor PT100 (X60.1 X60.4) Check wiring and sensor
Open-circuit Pt100 Sensor
Open-circuit sensor PT100 (X60.1 X60.4) Check wiring and sensor
Open-circuit Pt 100 Sensor (Line
Open-circuit compensation line of sensor
Compens)
PT100 (X60.2 X60.4)
Meaning for the LMV5x system
Troubleshooting
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
*1)
*1)
*1)
*1)
*1)
Check wiring and sensor
CC1P7550en
01.10.2003