Direction Of Rotation; Reset; Operational Status Indication By Led On The Actuator; Power Is Fed To Unaddressed Actuator - Siemens LMV5 Series Basic Documentation

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Direction of rotation

Reset

Operational status indication
by LED on the actuator
Power is fed to
unaddressed actuator
Button for addressing is
pressed (display during
addressing procedure)
Addressing completed,
normal operation of actuator
104/278
Siemens Building Technologies
HVAC Products
To select the direction of rotation, choose the following menu on the AZL5...:
«Params & Display» → «Actuators» → «DirectionRot»
You are given the choice of «Standard» and «Reversed»:
Standard (counterclockwise)
90°
Facing the end of the drive shaft (not mounted)
To check the direction of rotation, every actuator can be moved in the home position in
fault-free standby mode.
The parameter is filed in the basic unit so that the direction of rotation need not be
reentered when replacing the actuator.
After setting the ignition positions or curves, the direction of rotation can
Note:
only be changed after deleting the curves and ignition positions on setting
menu «Delete Curves».
This facility makes it possible to reset an already addressed actuator in the case of a
replacement, repair, or if addressing is wrong (wrong address assignment by the user).
For that purpose, the user must press the actuator's addressing button for at least 10
seconds when the actuator is in normal operation. The actuator will then reset its
address which is indicated by the LED when steady on.
LED steady ON
ON
OFF
The actuator gives the addressing number via the LED. The blink interval is 200
ms:
1 pulse
2 pulses
3 pulses
4 pulses
5 pulses
6 pulses
After each blink cycle, there is a pause of 1.2 seconds.
Example of an actuator for gas
ON
OFF
Basic Documentation LMV51...
7 Display and operating unit AZL5...
Reversed (clockwise)
air actuator
gas actuator
oil actuator
auxiliary actuator
auxiliary actuator 2
auxiliary actuator 3
90°
7550d29/0903
7550d11E
Time
7550d12E
Time
CC1P7550en
01.10.2003