USER INTERFACE
Connected (Green): The UbiquiSTAT™ has detected a valid network connection. For BACnet MS/TP, this means
that the device has successfully joined the token ring.
Troubleshoot (Yellow): The UbiquiSTAT™ is able to communicate, but is detecting problems with the network that
may cause the communication to be unreliable. Check the RS-485 wiring and network confi guration on other
devices.
Disconnected (Red): The UbiquiSTAT™ has not detected a valid network connection. For BACnet MS/TP this
means the device has not joined the token ring.
- Activity: There are two indicator lights; one for data received (Rx), and one for data transmitted (Tx). These lights
blink whenever data is received or transmitted to or from the device respectively. They are useful as a basic
diagnostic in determining whether data is fl owing across the network.
- Rx Traffi c: This is a statistic that indicates how much network traffi c has been received by the UbiquiSTAT™.
Shown are both the number of messages and the total number of bytes. This number should be increase whenever
the thermostat is monitored or programed via the network (Gateway and/or Ubiquity
- Tx Traffi c: This is a statistic that indicates how much network traffi c has been transmitted by the UbiquiSTAT™.
Shown are both the number of messages and the total number of bytes. This number should be increase whenever
the thermostat is monitored or programed via the network (Gateway and/or Ubiquity
- Last Traffi c: This shows the time stamp of the last time network traffi c was received by the UbiquiSTAT™.
- Clear: This button clears the network traffi c statistics. This includes: Rx Traffi c, Tx Traffi c, and Last Traffi c.
• Other:
- USB Activity: This indicator light is lit whenever there is traffi c detected on the USB port.
- Network Override: This indicator light is lit whenever any of the BACnet objects are being commanded remotely
from the network. This occurs, for example, whenever a sub system is implemented for the network through
Ubiquity
. The internal BACnet explorer screen can be used to determine precisely which BACnet object(s) is/are
TM
being externally commanded
4.3

SERVICE STATUS

Service Status is defined as a state of the controller or HVAC equipment that requires action by the end user to resolve.
When a service status is active, a red badge is visible on the top of the home screen to the right of the TCS logo.
Touching this badge presents the service status viewer, which shows all active service statuses and when they were
detected. The UbiquiSTAT™ may be configured to report the following service conditions:
Fan Proving Failure: When a DI is configured for Fan Proving, the system will shut down if the fan is not detected as
operational after a call from the controller. More information on this feature can be found in
proving status can be reset from the service status screen, thereby re-enabling system control.
Check Filter: When a DI is configured for Check Filter, service status will indicate the need to replace the air filter.
The Check Filter status is present whenever the DI is active, and is absent when the DI is inactive. This status is
automatically cleared when the filter is changed and the status becomes inactive.
Discharge High: When the discharge temperature exceeds the high limit value, the heat control is shut down until the
condition no longer exists.
Discharge Low: When the discharge temperature drops below the low limit value, the cool control is shut down until
the condition no longer exists.
DI1 - DI3: When a DI is configured for reporting service status, it indicates when the DI is active. A text message can
be customized for each DI.
4.4

ABOUT SCREEN

This screen shows basic information about the UbiquiSTAT™ including:
• Model
• Device Name
• Device ID
• Serial Number
• Firmware Version
• Hardware Version
2800 Laura Lane Madison, WI 53562 | 800.288.9383 Fax: 608.836.9044 | www.tcsbasys.com
(see section
4.5.2.6).
).
TM
).
TM
section
5. The fan
18

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Us4010Us4020Us4040Us4050

Table of Contents