Flexible safety unit / safety guard switching unit
Hide thumbs Also See for G9SX Series:

Advertisement

LED Indicators
Marking
Color
Name
Power supply
PWR
Green
indicator
Safety input 1
T1
Orange
indicator
Safety input 2
T2
Orange
indicator
Feedback/
FB
Orange
reset input
indicator
Logical AND
AND
Orange
input indicator
Logical AND
AND1
Orange
input indicator
Logical AND
AND2
Orange
input indicator
Safety output
EI
Orange
indicator
OFF-delayed
ED
Orange
safety output
indicator
Error indicator ❍
ERR
Red
* Refer to Fault Detection on the next page for details.
Settings Indication (at Power ON)
Settings for the G9SX can be checked by the orange indicators for approx. 3 seconds after the power is turned ON. During this settings indication
period, the ERR indicator will light, however the auxiliary error output will remain OFF
Indicator
Item
T1
Cross fault detection mode
FB
Reset mode
AND
Logical AND connection input
(AND1,
mode
AND2)
G9SX-AD G9SX-ADA G9SX-BC G9SX-EX G9SX-EX-T
---
---
---
---
---
---
---
Setting position
Y1 terminal
T32 or T33 terminal
Logical AND
connection preset
switch
Lights up while power is
supplied.
Lights up while a HIGH state
signal is input to T12.
---
---
Blinks when an error relating to
safety input 1 occurs.
Lights up while a HIGH state
signal is input to T22.
---
---
Blinks when an error relating to
safety input 2 occurs.
Lights up in the following cases:
• With automatic reset while a
HIGH state signal is input to
T33.
• With manual reset while a
---
---
HIGH state signal is input to
T32.
Blinks when an error relating to
feedback/reset input occurs.
Lights up while a HIGH state
signal is input to T41.
---
---
Blinks when an error relating to
logical AND connection input
occurs.
Lights up while a HIGH state
signal is input to T41.
---
---
Blinks when an error relating to
logical AND connection input
occurs.
Lights up while a HIGH state
signal is input to T51.
---
---
Blinks when an error relating to
logical AND connection input
occurs.
Lights up while the
Instantaneous safety outputs
(S14, S24, S34) are in the
---
ON-state.
Blinks when an error relating to
the instantaneous safety
output occurs.
Lights up while OFF-delayed
safety outputs (S44, S54) are
in the ON-state.
---
Blinks when an error relating to
OFF-delayed safety output
occurs.
Lights up or blinks when an
error occurs.
Indicator
Setting mode
status
Lit
Cross fault detection mode: ON
Not lit
Cross fault detection mode: OFF Y1 = 24 VDC
Lit
Manual reset mode
Not lit
Auto reset mode
Lit
Enable logical AND input
Not lit
Disable logical AND input
G9SX
Function
Reference
---
*
Setting status
Y1 = open
T33 = 24 VDC
T32 = 24 VDC
"AND"
"OFF"
13