Limitless™ WDRR Receiver
7
CONFIGURATION MODES AND OPERATIONS
The configuration LEDs
function button
.The different configuration modes will be defined in detail throughout sections 7.1 to 7.6 with a
one-page summary chart following section 7.6. This chart is labeled as Figure 7 (Limitless™ WDRR Operation
and LED Functions Chart) and can be used as a quick reference chart for the detail defined in section 7.
7.1 Start-up or Re-start Sequence Mode
Zero switches paired to the WDRR: The configuration LEDs will turn on for a few seconds while the WDRR
performs a channel scan. Afterwards, all configuration LEDs will turn off and only the green power LED will be
illuminated. This indicates power is supplied to the Limitless™ WDRR, and the unit is ready to use.
One or more switches paired (per Section 7.3) to the WDRR: The configuration LEDs will turn on for a few
seconds while the WDRR performs a channel scan. The WDRR receiver will enter system check mode for up to
two minutes. The red, yellow, and green configuration LEDs will illuminate sequentially until the system check is
successfully completed. Afterwards, all configuration LEDs will turn off, and the green power LED will be lit
indicating power is supplied to the WDRR. The Limitless™ WDRR is ready to use, and will also display the status
of tri-color output LEDs , low battery output LED , and lost RF signal output LED assuming the RF Link
switch is in position "0".
ATTENTION
If there are multiple WDRRs being used in the application, apply power to previously paired WDRRs
first (if any) and then to one WDRR at a time. Allow time for each WDRR to complete its start-up
sequence before applying power to the next WPMM.
7.2 Set-up Mode
The Set-up Mode allows the "normal" output indication and NPN/PNP electrical output to be reversed for all of the
Limitless™ inputs. This set-up mode can only be utilized before any Limitless™ input is paired (see Section 7.3) to
the WDRR. Once a Limitless™ input has been paired, you will no longer be able to access the Set-up Mode and
a Factory Reset will need to be conducted to again allow access to the Set-up mode (see Section 7.5).
Example: The Limitless™ input is a WGLA Series switch with a pin plunger actuator. Normal operation has the pin
plunger actuator not depressed, the tri-color output LED is green; then, once actuated the LED turns red, and the
NPN/PNP electrical output will change state. The set-up mode allows this indication to be reversed by having the
red tri-color output LED on when the plunger actuator is not being depressed. The NPN/PNP electrical output will
also be reversed.
Step
Action
Completely read this procedure before starting to understand the timing of events needed to be performed.
1
Press the Function button
2
will flash. Immediately release the function button. The red LED will illuminate with a short flash off every
second.
To reverse the output indication and associated electrical state: Actuate the function button
3
release. The red LED will be off with a short flash on every second. In the next five seconds, actuate and
release the function button
Limitless™ output being "normal" or "reversed". Once the desired output indication and state has been
chosen, wait approximately 5 seconds for all configuration LEDs to turn off before proceeding with other
configuration modes.
will display different modes of operation and actions when used in conjunction with the
on WDRR for >1 to <4 seconds at which time the green configuration LED
again (within 5 second intervals). This will cause the toggling between the
50063987
Issue 1,
once and
Honeywell Sensing and Control 17