Limitless™ WDRR Receiver
7

CONFIGURATION MODES AND OPERATIONS

The configuration LEDs
function button
.The different configuration modes will be defined in detail throughout sections 7.1 to 7.6 with a

one-page summary chart following section 7.6. This chart is labeled as Figure 7 (Limitless™ WDRR Operation
and LED Functions Chart) and can be used as a quick reference chart for the detail defined in section 7.

7.1 Start-up or Re-start Sequence Mode

Zero switches paired to the WDRR: The configuration LEDs  will turn on for a few seconds while the WDRR
performs a channel scan. Afterwards, all configuration LEDs  will turn off and only the green power LED  will be
illuminated. This indicates power is supplied to the Limitless™ WDRR, and the unit is ready to use.
One or more switches paired (per Section 7.3) to the WDRR: The configuration LEDs  will turn on for a few
seconds while the WDRR performs a channel scan. The WDRR receiver will enter system check mode for up to
two minutes. The red, yellow, and green configuration LEDs  will illuminate sequentially until the system check is
successfully completed. Afterwards, all configuration LEDs  will turn off, and the green power LED  will be lit
indicating power is supplied to the WDRR. The Limitless™ WDRR is ready to use, and will also display the status
of tri-color output LEDs , low battery output LED , and lost RF signal output LED  assuming the RF Link
switch  is in position "0".
ATTENTION
If there are multiple WDRRs being used in the application, apply power to previously paired WDRRs
first (if any) and then to one WDRR at a time. Allow time for each WDRR to complete its start-up
sequence before applying power to the next WPMM.

7.2 Set-up Mode

The Set-up Mode allows the "normal" output indication and NPN/PNP electrical output to be reversed for all of the
Limitless™ inputs. This set-up mode can only be utilized before any Limitless™ input is paired (see Section 7.3) to
the WDRR. Once a Limitless™ input has been paired, you will no longer be able to access the Set-up Mode and
a Factory Reset will need to be conducted to again allow access to the Set-up mode (see Section 7.5).
Example: The Limitless™ input is a WGLA Series switch with a pin plunger actuator. Normal operation has the pin
plunger actuator not depressed, the tri-color output LED is green; then, once actuated the LED turns red, and the
NPN/PNP electrical output will change state. The set-up mode allows this indication to be reversed by having the
red tri-color output LED on when the plunger actuator is not being depressed. The NPN/PNP electrical output will
also be reversed.
Step
Action
Completely read this procedure before starting to understand the timing of events needed to be performed.
1
Press the Function button
2
 will flash. Immediately release the function button. The red LED will illuminate with a short flash off every
second.
To reverse the output indication and associated electrical state: Actuate the function button
3
release. The red LED will be off with a short flash on every second. In the next five seconds, actuate and
release the function button
Limitless™ output being "normal" or "reversed". Once the desired output indication and state has been
chosen, wait approximately 5 seconds for all configuration LEDs to turn off before proceeding with other
configuration modes.
will display different modes of operation and actions when used in conjunction with the

on WDRR for >1 to <4 seconds at which time the green configuration LED

again (within 5 second intervals). This will cause the toggling between the

50063987
Issue 1,
once and

Honeywell Sensing and Control 17