Enthalpy Settings; Single Enthalpy Curve Boundaries; Single Enthalpy And Dual Enthalpy High Limit Curves - Carrier 50FC Series Service And Maintenance Instructions

Single package rooftop electric cooling unit
Table of Contents

Advertisement

Enthalpy Settings

When the OA temperature, enthalpy and dew point are below
the respective setpoints, the Outdoor Air can be used for econ-
omizing. Figure 73 shows the new single enthalpy boundaries
in the W7220. There are 5 boundaries (setpoints ES1 through
ES5), which are defined by dry bulb temperature, enthalpy and
dew point.
Refer to Table 13 for ENTH CURVE setpoint values.
The W7220 calculates the enthalpy and dew point using the
OA temperature and humidity input from the OA enthalpy sen-
sor. When the OA temperature, OA humidity and OA dew
ECONOMIZING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
ENTHALPY
TEMP. DRY
CURVE
BULB (F)
ES1
80
ES2
75
ES3
70
ES4
65
ES5
60
HL
86
Fig. 73 — Single Enthalpy Curve Boundaries
Table 13 — Single Enthalpy and Dual Enthalpy High Limit Curves
TEMP.
ENTHALPY
DEWPOINT (F)
(btu/lb/da)
60
57
54
51
48
66
point are all below the selected boundary, the economizer sets
the economizing mode to YES, economizing is available.
When all of the OA conditions are above the selected bound-
ary, the conditions are not good to economize and the mode is
set to NO.
Figure 73 shows the 5 current boundaries. There is also a high
limit boundary for differential enthalpy. The high limit bound-
ary is ES1 when there are no stages of mechanical cooling en-
ergized and HL (high limit) when a compressor stage is
energized.
POINT P1
TEMP. (F)
28.0
80
26.0
75
24.0
70
22.0
65
20.0
60
32.4
86
48
DUAL ENTHALPY
HIGH LIMIT
SINGLE ENTHALPY
P2 (T,RH)
P1
(T,RH)
ES4
ES2
ES5
ES3
POINT P2
HUMIDITY
TEMP. (F)
(%RH)
36.8
66.3
39.6
63.3
42.3
59.7
44.8
55.7
46.9
51.3
38.9
72.4
ES1
HL
HUMIDITY
(%RH)
80.1
80.0
81.4
84.2
88.5
80.3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents