Troubleshooting The Ecm Motor; Fault Condition/Reset Trigger - Carrier 50FC Series Service And Maintenance Instructions

Single package rooftop electric cooling unit
Table of Contents

Advertisement

RPM
Field Accessories:
1 Stage E Heat
2 Stage E Heat
NOTE: Values in the Field Accessories section are VDC adders.
Fig. 9 — Example of Fan Speed Set Up Labels for SystemVu™ Controls

TROUBLESHOOTING THE ECM MOTOR

EcoBlue™ motors are designed with several built-in protections
included in the motor software. If the motor detects a fault it will
safely shut down. For temperature related faults the motor re-
quires a line voltage reset to continue operation. For all others,
the motor will resume operation automatically as soon as the
fault condition is cleared. See Table 2 for a complete list.
Table 2 — Fault Condition/Reset Trigger
Fault
Reset
Condition
Trigger
Phase Failure
Automatic
Locked/ Blocked
Automatic
Rotor
Motor Over
Manual
Heated
Power Module
Manual
Over Heated
Line under-
Automatic
voltage
Communication
Automatic
Error
Calculator
0.2
0.4
1301
1477
1639
1500
1381
1544
1699
1625
1463
1615
1763
1750
1548
1688
1828
1875
1633
1764
1897
2000
1720
1842
1967
2125
1808
1921
2040
2250
1897
2003
2115
2375
1987
2068
2191
2500
66
66
Economizer
80
80
107
107
107
Description
One phase is missing or imbalanced. In
this case the motor will come to a stop
and then automatically restart when all
phases are present.
The rotor is blocked. Once the locking
mechanism has been removed, the
motor will automatically restart.
The motor will stop in the event the
motor over heats. In this case there has
to be a manual restart.
The motor will stop in the event the
electronics over heat. In this case there
has to be a manual restart.
Once the line voltage returns within
permitted operating range, the fan will
automatically restart.
Internal communication error of the
fan's electronics. The fan will restart
automatically, if error is cleared.
ESP in. wg
0.6
0.8
1.0
1.2
1788
1925
2054
1843
1976
2101
1902
2031
2152
1962
2087
2206
2025
2146
2262
2090
2208
2320
2157
2271
2380
2227
2336
2298
66
66
66
66
80
80
80
80
107
107
107
Troubleshooting the motor requires a voltmeter.
1.
Disconnect main power to the unit.
2.
Disconnect motor plug in supply section of the unit.
3.
Restore main unit power.
4.
Check for proper line voltage at motor power leads Black
(PL1-1), Yellow (PL1-2), and Blue (PL1-3). Blue is only
present on 3-phase motors. See the following table.
50FC Unit Voltage
208/230
460
575
5.
Disconnect main power.
6.
Reconnect motor plug in supply section of unit.
7.
Restore main power.
8.
Check for proper motor control voltage signal of 9.7Vdc
to 10.3Vdc at IFM-1 and IFM-3 on Unit Control Board
(UCB). See Fig. 10.
9.
Using a jumper wire from unit control terminals R to G,
engage motor operation.
10. Verify control signal from user speed selection switch by
placing voltmeter taps in provided terminals marked Vdc.
Signal should be between 3.8Vdc and 10.3Vdc.
11. If the motor does not start and run, remove the fan assem-
bly and replace the motor with one having the same part
number. Do not substitute with an alternate design motor
as the voltage/speed programming will not be the same as
that on an original factory motor.
7
1.4
1.6
1.8
2.0
2174
2289
2220
2332
2268
2378
2318
2372
66
66
80
80
107
107
Motor Voltage
230
460
575
Min-Max Volts
187-253
360-506
517-633

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents