Actuator Wiring (Three-Position) - Siemens OpenAir GBB Series Technical Basics

Rotary actuators without spring return
Hide thumbs Also See for OpenAir GBB Series:
Table of Contents

Advertisement

Line length for actuators
connected in parallel
Assumption
Actuators with three-
position control
GBB13..1
Power consumption and
perm. voltage drop with
one actuator
P&I diagram:
Currents at AC 24 V
Example:
Parallel connection
of two actuators
24/44
Siemens
Smart Infrastructure
The following sections show how to determine the permissible line length and cross-
sectional areas for the various actuators based on examples.
The examples for actuators connected in parallel apply to the following arrangement:
L1
Controller
L1
The line resistances of L2 are equal and can be ignored for L1. Separately calculate the
permissible line lengths L2 for other connections (ring, star-like).
6.2

Actuator wiring (three-position)

With three-position actuators, only the situation as presented under AC 24 V is
important. Sizing takes place via lines 1 (G), 6 (Y1), and 7 (Y2).
The table shows the power consumption of an actuator as well as the permissible
voltage drop.
Operating
Power
voltage/pos. signal
consumption
AC 24 V
7 VA
The diagram shows the currents in the connecting lines for one actuator.
AC 24 V
AC 0.29 A
1
0 V
6
Open
7
Determining the line lengths for two actuators GBB/GIB13..1 and AC 24 V supply.
Only the currents in line 1 (G) and 6 (Y1) or 7 (Y2) determine the line sizing.
Max. permissible voltage drop = 4 % per line (total 8 %).
·
Consumption = 2 x 7 VA = 14 VA
·
Line current = 2 x 0.29 A = 0.58 A
Max. permissible single line length: 140 m at 1.5 mm
Rotary actuators without spring return GBB/GIB..1
Wiring notes
G0
L2
A1
G
G0
G
L2
A2
G0
G
G0
G
L2
A3
G0
G
G0
L2
A4
G
Perm. voltage drop for line
1 (G), 6 (Y1), 7 (Y2)
D
U/U = max. 8 % (4 % each per line)
GBB13...
G
M
Y1
Y2
2
cross-sectional area.
CE1Z4626en
2019-11-28