85° Switching hysteresis 2° WARNING: Apply only line voltage or only Class 2 voltage to the switching outputs of both auxiliary switches A and B. Mixed operation is not permissible. See Wiring for details. Page 2 Siemens Building Technologies, Inc.
Page 3
Life cycle Designed for over 60,000 full strokes and a minimum of 1.5 million repositions at rated torque and temperature Noise level <45 dBA (running) Dimensions See Figure 24. Weight 4.4 lbs (2 kg) Siemens Building Technologies, Inc. Page 3...
Page 4
Kit contains: • Crank arm to attach to the splined hub of the shaft adapter • Mounting bracket • Required mounting fasteners Figure 4. Crank Arm Kit with Mounting Bracket. Page 4 Siemens Building Technologies, Inc.
Page 5
GBB and GCA OpenAir actuators in an outside low temperature. Assembly Heating includes: Element • Weather Shield (ASK75.1U) • Heater Kit (985-105) Thermostat Figure 8. Heater/Weather Shield Assembly. 985-008: 1/2-inch (12 mm) for 1/2-inch NPT connector. Figure 9. Conduit Adapter. Siemens Building Technologies, Inc. Page 5...
SWITCH which a signal is to be given. Factory setting Switch A 5° Switch B 85° Figure 12. Dual Auxiliary Switch Dials. Siemens Building Technologies, Inc. Page 7...
The shaft adapter and mounting parts are shipped in a separate container with the actuator. • The actuator is shipped from the factory with a 5° pre-load to ensure tight close off of the damper. Page 8 Siemens Building Technologies, Inc.
Page 9
If the shaft adapter is not resting against the left raised stop, remove the adapter and insert it against the left stop. e. Place the position indicator to the "0" position on the outside scale. See Figure 18. Siemens Building Technologies, Inc. Page 9...
Page 10
8. Return the actuator to the damper shaft and tighten the shaft adapter to the damper shaft. PUSH Figure 19. Mechanical Range Adjustment. Reversing the position Reverse the position indicator so that the counterclockwise 0 to 90 scale is visible. indicator POSITION INDICATOR Figure 20. Position Indicator. Page 10 Siemens Building Technologies, Inc.
Page 11
Switch B – Normally Closed Black/blue Switch B – Normally Open Black/pink Feedback Potentiometer 0 to 100% P1 – P2 White/red Feedback Potentiometer Common White/blue Feedback Potentiometer 100 to 0% P3 – P2 White/pink Siemens Building Technologies, Inc. Page 11...
Page 12
Apply a control signal (24 Vac) to wires 1 (red) and 7 (orange). The DMM should indicate contact closure as the actuator shaft coupling reaches the setting of switch A. Page 12 Siemens Building Technologies, Inc.
Dimensions 4-3/16 (106) OPENING FOR STANDARD 1/2" CONDUIT ∅ CONNECTOR (2) 8-1/4 1.04 (210) (26.5) 1-3/8 (35) 15-3/8 4-1/16 (390) (103) Figure 23. Dimensions of the ASK75.1U Weather Shield in Inches (Millimeters). Siemens Building Technologies, Inc. Page 13...
Page 14
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. OpenAir is a trademark of Siemens Building Technologies, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners.