Actuator Wiring (Modbus Rtu) - Siemens OpenAir GBB Series Technical Basics

Rotary actuators without spring return
Hide thumbs Also See for OpenAir GBB Series:
Table of Contents

Advertisement

Note
26/44
Siemens
Smart Infrastructure
6.4

Actuator wiring (Modbus RTU)

The damper actuators are supplied with a prewired connecting and communication
cable. All interconnected devices must be connected to the same G0.
Strand code
Strand color
1
red (RD)
2
black (BK)
6
violet (VT)
8
grey (GY)
9
pink (PK)
The operating voltage at terminals G and G0 must comply with the requirements under
SELV or PELV.
Safety transformers with twofold insulation as per EN 61558 required; they must be
designed to be on 100 % of the time.
Rotary actuators without spring return GBB/GIB..1
Wiring notes
Terminal code
Description
G
System potential AC 24 V
G0
System neutral AC 24 V
REF
Reference (Modbus RTU)
+
Bus + (Modbus RTU)
-
Bus - (Modbus RTU)