Quick Installation

Hardwire the UPS System's
1
input terminals to a utility
power source.
HIGH VOLTAGE! RISK OF SERIOUS INJURY OR
DEATH! FOR QUALIFIED ELECTRICIANS ONLY!
ELECTRICIANS MUST READ WARNINGS BELOW
AND IN SAFETY SECTION PRIOR TO
Model
SMX5000XLRT3U
Before hardwiring, switch OFF the facility's circuit breaker which is supplying power to the circuit
the UPS System will be connected to. Using a screwdriver, remove the top of the box
the UPS System's input terminals. Pass user-supplied cable through the opening in the box
and attach it to the terminals. After hardwiring is complete, switch ON the facility's circuit breaker
which is supplying power to the circuit the UPS System is connected to. Please note that after the
UPS System is connected to a live utility power source, the UPS (in "Standby" mode) will
automatically charge its batteries,* but will not supply power to its outlets until it is turned ON
(see Step 3 below).
* The BATTERY CHARGE LED will be the only LED illuminated.
Note: UPS system will function properly upon initial startup; however, maximum runtime for the unit's battery
will only be accessible after it has been charged for 24 hours.
• Wiring must be done by a qualified electrician.
• When making wiring connections, observe the cable connection regulations appropriate to
your area at all times. Be sure to install an easily accessible disconnect switch in your
installation wiring so you may cut off the UPS's AC input during fires and other
emergencies. Ensure that cables are fitted with cable sleeves and are secured by
connector clamps. Tighten connections with a torque of not less than 10 inch-pounds
(1.1 NM).
• Make sure that your equipment is properly grounded.
• Using cables of improper size may damage your equipment and cause fire hazards.
Choose appropriate cabling and protection circuits to make wiring connections (Ground
conductors must be the same size and type as the power conductors used).
18-08-323-932460.indb 5
DANGER!
INSTALLATION.
Input and Output Ratings
Voltage
Input Current
230V
HARDWIRE WARNINGS!
1
Output Current
27A
30A
5
A
B
Wire Size
10 AWG
covering
A
B
2/13/2019 2:53:45 PM