Installing Burner - Slant/Fin EUTECTIC EC-10DV Series Installation And Operating Instructions Manual

Direct vent oil-fired water boiler/no. 2 oil
Hide thumbs Also See for EUTECTIC EC-10DV Series:
Table of Contents

Advertisement

EUTECTIC EC-10 DV
Automatic
Air Vent
1-1/4"
NPT
Supply
Figure 3. Air Eliminating System or Alternating Collecting System. Pipe off to a safe place the relief valve and drain outlet.
If system pressure needs further control, add an additional tank or install a
larger capacity tank. The automatic air vent should be installed in the top of
the boiler, as in figure 3.
B. CONVENTIONAL COMPRESSION TANKS (non-diaphragm type) are
used to control system pressure in an AIR COLLECTING SYSTEM. Within
the system, after initial start-up and venting, air is collected in the tank and
acts in contact with the water to control pressure. Air is not vented from this
system. If system pressure needs further control, add another tank in
parallel with the original tank or install a large capacity tank. Locate the
tank at the inlet end of the pump near the boiler. (See figure 3)
C. HOT WATER RADIATION VENTING - Manual air vents should be installed
at the top of all "drops" (where piping goes downward). Air must be vented
or purged from all zone lines to permit proper system heating.
D. PUMP LOCATION - Locating low-head pump(s) on return to boiler is
acceptable for smaller boiler sizes in residences of one or two stories.
The pump location shown in figure 3 is required in large, multi-story
building installations, especially when high-head pumps are used.
IMPORTANT: Hot water heating systems containing high water volume, such
as would occur with cast iron radiation, require special care with air elimina-
tion. The circulator pump should be located on the boiler supply pipe and the
expansion tank and air scoop should be located near the pump suction.
INSTALLING THE BURNER
See Burner Data, pages 12-13, and Burner Manual supplied with burner. If
burner is not mounted as received, mount to boiler, placing flange over
mounting studs. Use gasket between flange and boiler. Distance between
flange and nose of burner must be as shown in table on page 12 (Burner
Insertion Depth). Check to see that nozzle and settings are as given in burner
data tables, pages 12-13.
Air Eliminator
as per Manufacturer
Specifications
To Circ. (s)
and Zones
Suppy Pipe Mounted
Tridicator
Relief valve 3/4
Panel Mounted
Tridicator Temperature
Sensor Well
13-31/32
7-11/16
VOLUME OF WATER IN STANDARD PIPE OR TUBE
Standard Steel Pipe
Nominal
Pipe
Pipe ID
pipe Dia.
Schedule
Inch
3
8
1
40
0.622
2
5
8
3
40
0.824
4
1
40
1.049
1
40
1.380
1
4
1
1
40
1.610
2
2
40
2.067
2
1
40
2.469
2
3
40
3.068
BURNER INSERTION DEPTH
WATER CONTENT OF BOILER (GALLONS)
EC-13
EC-14
EC-15
5
6.5
8
Panel Mounted
Tridicator Pressure
Sensor Well
1/2" NPT Tapping
for Feed Valve and
Expansion Tank
1-1/4 NPT
return tapping
Drain outlet
Copper Pipe
Gal. per
Pipe ID
Gal. per
Lin.Ft.
Inch
Lin. Ft.
0.430
0.0075
0.0157
0.545
0.0121
0.666
0.0181
0.0277
0.785
0.0251
0.0449
1.025
0.0429
0.0779
1.265
0.0653
0.106
1.505
0.0924
0.174
1.985
0.249
2.465
0.384
2.945
EC-16
8.5
5
0.161
0.248
0.354