Property
Climatic environmental
conditions
Mechanical environmental
conditions (shocks and
vibrations)
Protection against chemical
substances
Biological environmental
conditions
Cooling air
Pollution
Approvals
UL, cUL, CE, c-tick, SEMI
F47.
PM250 Power Module
Hardware Installation Manual, 01/2016, A5E36265179B-AA
Version
Better than 3K3 according to EN 60721-3-3
Temperature range without derating
•
–
LO base load power
–
HO base load power:
Temperature range with derating
•
–
LO/HO base load power:
Restrictions for special ambient conditions (Page 61)
Relative humidity: 5 ... 95%, condensation not permitted
•
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
•
water and water jets are not permitted
The device is suitable for operation in mechanical environmental conditions that conform
with 3M1 according to EN 60721-3-3
Vibration test according to IEC 60068-2-6 with 10 vibration cycles per axis
•
–
in the range 10 Hz ... 57Hz with a deflection of 0.075 mm
–
in the range 57 Hz ... 150Hz with an acceleration of 1 g
Shock resistance according to IEC 60068-2-27 with three impulses per axis in both direc-
•
tions
–
Peak acceleration: 5 g
–
Duration: 30 ms
protected against damaging chemical substances that conform with 3C2 according to EN
60721-3-3
suitable for operation in biological environmental conditions that conform with 3C2 according
to EN 60721-3-3
clean and dry air
suitable for environments with degree of pollution 2 according to EN 61800-5-1, condensa-
tion not permitted
The drive only satisfies the UL requirements when UL-certified fuses are used.
1)
0 °C ... +40 °C
0° C ... +50° C
1)
0 °C ... +60 °C
Technical specifications
7.3 General data