P010: Language; P838 Auto False Echo Suppression - Siemens SITRANS L Series Operating Instructions Manual

Radar transmitters, probe with ma/hart
Hide thumbs Also See for SITRANS L Series:
Table of Contents

Advertisement

Commissioning
6.2 Local commissioning
6.2.11.7

P010: Language

The parameter title appears in the language selected, for parameters P000 to P010. If a
language is selected, parameter titles for the Quick Start parameters are displayed in the
auxiliary reading field.
Parameter
P010
Parameter
P000
P001
P003
P004
P005
P006
P007
P010
6.2.11.8

P838 Auto false echo suppression

Enable False-Echo Suppression (P837: Auto False-Echo Suppression)
P837 instructs SITRANS Probe LR to learn the echo profile at that moment, and use the
learned profile instead of the default TVT curve.
Parameter
P837
Set up Auto False-Echo Suppression:
● Perform this function when the vessel is empty or nearly empty.
● First rotate the instrument for best signal (lowest false-echo amplitude)
● Determine distance from reference point to material level and subtract 0.5 m (1.6 ft).
● Press PROGRAM
● Select P838, key in [distance to material level minus 0.5 m/1.6 ft], and press ENTER .
● Select P837.
● Press 2 and then press ENTER
TVT) after a few seconds.
● Press PROGRAM to return to RUN mode.
38
Value
Description
0
*
Numeric/None
1
English
2
German
3
French
4
Spanish
Auxiliary reading
LOCK
OPERATION
MEAS RESP
ANTENNA
UNITS
EMPTY
SPAN
LANGUAGE
Value
Description
0
Off
1
*
Use "Learned" TVT
2
"Learn"
, then DISPLAY
.
. P837 will automatically revert to 1 (use Learned
Operating Instructions, 05/2019, A5E32337711-AC
SITRANS Probe LR with mA/HART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr7ml5430

Table of Contents