Overview of installation location requirements
125 mm
or more
(recommended)
You can select the direction of
draining (left or right).
Maximum pipe length: 15 m
Make at least one round to
reduce noise and vibration.
The actual units may look different from
the images depicted here.
Model
AC026/035TNXDKG
AC052TNXDKG
AC071TNXDKG
Outdoor
Unit
CAUTION
Outer wall
Indoor
Unit
Cut insulation to have
rainwater drained
CAUTION
•
Comply with the length and height limits described in
the figure above.
•
For the product that uses the R-32 refrigerant, Install
the indoor unit on the wall 1.8 m or higher from the
floor.
DB68-08947A-00_IM_CAC QMD_EU_EN_.indd 7
100 mm or more
(recommended) 125 mm
or more
(recommended)
Drain hose hole
Maximum pipe height: 8 m
(Unit : m)
Pipe length
Pipe height
Minimum Maximum
Maximum
3
20
15
3
30
20
3
50
30
Make a U-trap (A) on the
pipe (which is connected to
the indoor unit) at outer wall
and cut the bottom part of
the insulation (about 10 mm)
to prevent rainwater from
getting inside through the
insulation.
Step 1-2 Checking and preparing
accessories and tools
Accessories
Accessories in the indoor unit package
AC***TNXDKG
Mounting bracket (1)
AC026/035TNXDKG
Remote control (1)
General information (1)
Installation manual (1)
Extra M4 x 12
tapping screw (2)
Tools
General tools
•
Vacuum pump
•
(Backward flowing
•
prevention)
•
•
Manifold gauge
•
•
Stud finder
•
•
Torque wrench
•
•
Pipe cutter
•
•
Reamer
Tools for test operation
•
Thermometer
•
•
Resistance meter
Mounting bracket (1)
AC052/071TNXDKG
Remote control battery (2)
Quick guide (1)
Holder remocon (1)
Pipe bender
Spirit level
Screwdriver
Spanner
Drill
L-wrench
Measuring tape
Electroscope
English
7
2020-02-10 오전 11:14:27