Installation
Note for IR 180 UP: The installation
position should be at least 1 m from a
light, since heat radiation may trigger
the system.
Installation procedure:
1. Pull the mains lead out of the fl ush
box and strip the insulation from
the individual leads.
Connecting the supply lead
(refer to Ill. on page 4)
The mains lead consists of a 3-phase
cable.
L = phase conductor
(usually black or brown)
N = neutral conductor
(usually blue)
L' = phase conductor
(usually black or brown)
If in doubt, the cable must be identi-
fi ed with a voltage tester. Switch OFF
the current again. Phases (L) and (L')
in addition to the neutral conductor
(N) are connected to the terminal
block. A protective-earth conductor is
not required.
Important: Reversing the connections
may result in damage to the unit.
(IR 180 UP / HF 360 UP)
2. Push the basic element
into the
fl ush box
and arrange horizontal-
ly. Take care that the cables are not
pinched. Tighten both screws on
the expansion claw until the basic
element is fi rmly seated or screw
with socket fi xing screws on the
support ring.
3. Apply the cover frame
and sur-
round
and carefully mount the
sensor unit
without tilting.
4. Once the mains connection has
been made, the sensor switch can
be operated (refer to Functions
section).
The adjustment controls for the func-
tions are concealed behind the folding
design shade. Push in the catch on
the sensor unit with a screwdriver and
fold the design shade forwards.
Note:
Parallel switching of IR 180 UP and
HF 360 UP is possible. Nevertheless,
a neutral lead must be present on
each concealed box. The max. output
to be switched does not increase as a
result.
- 16 -
Functions
Reach setting (sensitivity)
The term reach denotes the approximately
circular diameter that results as the detection
zone. Adjusting screw left stop position means:
minimum reach (approx. 1 m / factory setting).
Adjusting screw right stop position means:
maximum reach (approx. 8 m).
1 - 8 m
Twilight setting (Response threshold)
The desired sensor response threshold can be
adjusted continuously from approx. 2 lux to
2000 lux.
2
Adjusting screw right stop position means:
LUX
Daylight operation approx. 2000 lux (factory
setting). Adjusting screw left stop position
means: Night-time operation approx. 2 lux.
When adjusting the detection zone and for
the performance test in daylight, the adjusting
screw must be set to the right stop position.
2 - 2000 lux
Time setting (Switch-off delay)
The desired duration of illumination of the con-
nected light can be continuously adjusted from
approx. 5 sec. to max. 30 min.
Adjusting screw left stop position means:
shortest time approx. 5 sec. (factory setting)
30
Adjusting screw right stop position means:
longest time approx. 30 min.
The timer is restarted by any motion detected
before this time elapses. The shortest time set-
ting is recommended when adjusting the de-
5 sek. - 30 min.
tection zone and performing a functional test.
Note: After every off switching, further motion
detection is interrupted for approx. 2 seconds.
Only after this time elapses is it possible for the
Sensor Switch to switch light again.
(only for HF 360 UP)
- 17 -