Field Installed Electric Heat Kits
When Electric Heat Kits are installed into an Odyssey
Air Handler paired with a Symbio 700 controlled
condenser, configure the Symbio 700 controller so that
the electric heat control sequences and output signals
will be generated. Use the following steps and refer to
through .
1. In the Mobile Service and Installation app, tap
S S e e t t t t i i n n g g s s .
Figure 36. Edit configuration
40
2. Tap E E d d i i t t .
3. Tap P P r r i i m m a a r r y y H H e e a a t t i i n n g g S S o o u u r r c c e e .
4. Tap E E l l e e c c t t r r i i c c .
5. Tap P P r r i i m m a a r r y y H H e e a a t t i i n n g g S S o o u u r r c c e e .
6. Select 1 1 o o r r 2 2 .
7. Tap A A p p p p l l y y .
8. Verify that all settings are correct.