Secure The Vent Sections; Disassemble Vent Sections - Heat & Glo 6000CMOD-IFT Installation And Appliance Setup

Table of Contents

Advertisement

D. Secure the Vent Sections
• Vertical runs originating off the top of the appliance, with
no offsets, must be supported every 8 ft. (2.44 m) after
the maximum allowed 25 ft. (7.62 m) of unsupported rise.
• Vertical runs originating off the rear of the appliance, or
after any elbow, must be supported every 8 ft. (2.44 m).
• Horizontal runs must be supported every 5 feet (1.52
m).
• Vent supports or plumbers strap (spaced 120º apart)
may be used to support vent sections. See Figures 7.8
and 7.9.
• Wall shield firestops may be used to provide horizontal
support to vent sections.
• SLP ceiling firestops have tabs that may be used to
provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support could allow vent to sag and separate.
Use vent run supports and connect vent sections per in-
stallation instructions. DO NOT allow vent to sag below
connection point to appliance.
Figure 7.8 Securing Vertical Pipe Sections
Figure 7.9 Securing Horizontal Pipe Sections
Heat & Glo • 6000CMOD-IFT, 8000CMOD-IFT Installation Manual • 2509-980 Rev. L • 6/20
120º
120º
E. Disassemble Vent Sections
• Rotate either section (see Figure 7.10) so the seams on
both pipe sections are aligned as shown in Figure 7.11.
• Pull carefully to separate the pieces of pipe.
Figure 7.10 Rotate Seams for Disassembly
Figure 7.11 Align and Disassemble Vent Sections
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

8000cmod-ift

Table of Contents