You are directed through different configuration screens, depending on
the system being configured.
In a communication system that includes a communicating variable
speed air handler, heat kit configuration screens appear. See Figures
26–28.
HEAT KIT
6HKx6500206
BACK
DEFAULT
NEXT
A0627-001
FIGURE 26: Heat Kit Configuration - Screen 1
If you select a 13 kW heat kit or larger, there are two available stages of
electric heat. You must select the amount of electric heat that is applied
during a first-stage (W1) heat call. During a second-stage (W2) heat call,
the entire amount of electric heat available is applied. For a first-stage
(W1) heat call, it is best practice to only use the appropriate amount of
heat required to temper the air during an outdoor unit defrost cycle.
34
Johnson Controls Ducted Systems