5407934-UIM-C-1119
TABLE 7:
General System Settings (Continued)
Default
Name
Setting
Cycles per
4
Hour
Humidifier
No
Dehumidi-
No
fier
Max Heat
88°
Setpoint
Min Cool
52°F
Setpoint
AUX Heat
Off
Lockout
40
Available
Settings
4 or 6
Yes or No
NO,
OVERCOOL 1°F,
OVERCOOL 2°F,
OVERCOOL 3°F,
WITH EQUIP-
MENT
50°F to 88°F
52°F to 90°F
Off, 5°F, 10°F,
15°F, 20°F, 25°F,
30°F, 35°F, 40°F,
45°F, 50°F, 55°F
Explanation
This timer is set to four cycles per hour.
Fifteen minutes must elapse from the
start of one cycle before another can
start. A setting of six cycles per hour
requires 10 minutes before the next
cycle.
Enables or disables the humidifier. The
thermostat only activates the humidifier
if there is a demand for heating and
humidity.
If the NO option is selected, no dehu-
midification operation occurs. If you
select one of the OVERCOOL options,
the thermostat continues to run cooling
up to 1°F, 2°F, or 3°F below the setpoint
to meet the humidity setting of the
home. The WITH EQUIPMENT option
only applies to communicating systems.
The Humidistat Jumper setting on the
thermostat must be set to YES. The
control reduces the indoor airflow by
15% if there is a demand for both cool-
ing and dehumidification.
Allows you to define the maximum heat-
ing setpoint that is available
Allows you to define the minimum cool-
ing setpoint that is available
Applies to CONVENTIONAL ONLY.
Allows you to specify an auxiliary heat
lockout temperature. If the outdoor
ambient temperature is greater than the
selected auxiliary heat lockout tempera-
ture, the auxiliary heat (W1 and W2)
outputs are not energized.