TABLE 23: ID EEV Control
Fault (Displayed Text) Description
ID EEV: INVALID PRES-
SURE TRANSDUCER
ID EEV: INVALID SUC-
TION TEMP
ID EEV: FULLY OPEN IN
SUPERHEAT
ID EEV: SUCTION PRES-
SURE OUT OF RANGE
ID EEV: COMMUNICA-
TIONS LOST
TABLE 24: System Events
System Events: Logged but not shown in banner
Event (Displayed Text)
SETUP CORRECTION
OTA PASS (APPF)
OTA PASS (APPB)
OTA PASS (BOOT)
OTA TIMED OUT
FRONT BOARD CHANGED
AIR FILTER RESET
HUMIDIFIER FILTER RESET
UV LAMP RESET
EAC RESET
62
Invalid pressure transducer
Invalid suction temperature
Valve position to fully open while in
superheat control mode
Suction pressure out of range
RS-485 communication not sensed
Description
Setting was adjusted because it was out of
range or there was an issue with another related
setting
OTA software update for front PCB application
successful
OTA software update for back PCB application
successful
OTA software update for boot loader application
successful
OTA software update has timed out after 3
(15-minute) attempts
Front PCB has been changed with a new
unconfigured front PCB
Number of hours before air filter reminder
becomes active has been reset (from Filter
screen)
Number of hours before humidifier filter
reminder becomes active has been reset (from
Filter screen)
Number of hours before UV lamp reminder
becomes active has been reset (from Filter
screen)
Number of hours before EAC reminder
becomes active has been reset (from Filter
screen)