Final Finishing; Gas Specifications; Gas Inlet And Manifold Pressures; High Elevations - Vermont Castings Chateau DVT38S2 Installation Instructions And Homeowner's Manual

Direct vent decorative gas appliance
Table of Contents

Advertisement

������
�������
Fig. 7 Valve box framing.
If marble, tile or any other noncombustible decora-
tive face finish material is desired, a 3" (76mm) wide
noncombustible board (recommended Dura-Rock)
is to be nailed to the nailing flanges on both sides
of the unit. Also, 12" (305mm) of noncombustible
������
board is to be nailed to the front face of the U-chan-
��������� ��� �������
nel and the top framing member above the standoff.
���� ���
Combustible material can then be brought to the
outside edges of the noncombustible board installed
earlier. Any noncombustible decorative face finish
could be brought to the sides and top of the unit and
can cover the framing and sheet rock. If a decora-
tive facing is not desired, then the noncombustible
boards must be double thickness and brought flush
with the face of the unit.

Final Finishing

Noncombustible materials such as brick or tile may be
brought to the edges of the face of the appliance.
Gas Specifications
MODEL
FUEL
DVT38S2RN Natural Gas
DVT38S2RP
Propane
DVT38S2EN Natural Gas
DVT38S2EP
Propane

Gas Inlet and Manifold Pressures

Minimum Inlet Pressure
Maximum Inlet Pressure
Manifold Pressure
DVT38S2 Units: GFSN6Q3, GFSE6Q3
20009543
�����
�������
FP1362
MAX.
MIN.
GAS
INPUT
INPUT
CONTROL
B.T.U.H B.T.U.H.
Millivolt
56,000
38,000
Millivolt
56,000
45,500
24V Hi/Lo
56,000
38,000
24V Hi/Lo
56,000
45,500
Natural
LP (Propane)
5.5" w.c.
11.0" w.c.
14.0" w.c.
14.0" w.c.
3.5" w.c.
10.0" w.c.
Chateau™ Decorative Gas Appliance
DVT38S2
Certified To
ANSI Z21.50b-2005 / CSA 2.22b-2005
Vented Gas Fireplace

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).
WARNING: Improper installation, adjust-
ment, alteration, service or maintenance
can cause injury or property damage. Refer
to this manual for correct installation and
operational procedures. For assistance or
additional information consult a qualified
installer, service agency, or the gas supplier.

Gas Line Installation

When purging gas line the front glass must
be removed.
A gas shut off valve must be installed on
the gas pipe line going into the appliance
within easy access.
The gas pipeline can be brought in through the bottom
right side of the valve box assembly.
The gas line connection can be made with properly
tinned 1/2" copper tubing or 1/2" gas tight. Some
municipalities have additional local codes, it is always
best to consult your local authority and the CSA-B149.1
installation codes.
For USA installations consult the current National Fuel
Gas Code, ANSI Z223.1/NFPA 54.
1/2" NPT X 1/2" Flare
Shut-off Valve
1/2" Gas Supply
FP297A
Fig. 8 Typical gas supply installation.
1/2" Gas Tight or
Tinned Copper
(from valve)
(Not provided)
������
����� ���� ����
������ ��� ������
������
7