1 Phase Simplex
Control Panel for Grinder
and Vortex Pumps
Owner and Operational Manual
Pump 1 Seal Fail Probe:
The Seal Probe wires are connected to terminals 9 and 10 which are
labeled Pump 1 Seal Sensor. The Black wire from the Seal Probe is
connected to terminal 9 which is labeled BK for Black. The Yellow wire
from the Seal Probe is connected to terminal 10 which is labeled YW
Testing Seal Fail Probes:
#1. Put one ohm meter probe on the Black
wire of the sensor.
#2. Place the other ohm meter probe on the
"Hex" Nut portion of the sensor. The ohm
meter should read "continuity" or close to
zero ohms, If it reads "open" or "High" ohms
then the sensor is defective.
#3. Put one ohm meter probe on the seal
probe.
#4. Place the other ohm meter probe on the
yellow wire. The ohm meter should read
"continuity" or close to zero ohms, If it reads
"open" or "High" ohms then the sensor is
defective.
293 S. Wright St, Delavan, WI 53115 Phone: 1-866-973-6835 Fax: 800-426-9446
(Seal Fail may not be an option on your pump)
Seal Probe from pump
Seal Fail may not be an option on your pump.
#1.
0
#2.
Sensor is good:
0
Sensor is good:
Page 4 of 10
P10063VSM