Chapter 6. PDU specifications
This chapter contains the product specifications of the PDU.
Height
Width
Depth
Additional clearance
Length of power cord
Weight (including power cord)
Operating temperature at 0 - 1524 m (0 - 5000 ft) (room ambient)
Operating humidity
Shipping and storage temperature at 0 - 1524 m (0 - 5000 ft) (room
ambient)
Shipping and storage humidity
Localized air temperature in PDU
Rated voltage, rated current
192 - 400 V dc, 90 amps
Important: The PDU input power connection must be protected by
a 100 A circuit breaker.
Rated frequency
Direct current (dc) 0 Hz
Circuit breakers
Six double-pole branch rated circuit breakers rated at 15 amps.
Power outlets
Six Rong Feng RF-203P outlets rated at 15 amps (TUV/CSA)
The high-voltage dc power cord that comes with the PDU must be connected to a
properly wired and grounded high-voltage dc power source by a licensed
electrician. See "Connecting input power" on page 23 for additional information.
© Copyright IBM Corp. 2014
42 mm (1.65 in.)
444 mm (17.5 in.)
305 mm (12 in.)
25 mm (0.98 in.) for circuit breakers 3 mm
(0.12 in.) for outlets
4.3 m (14.1 ft.)
10 kg (22 lb)
5°C - 57°C (41°F - 134.6°F)
8% - 85% (noncondensing)
-40°C - 60°C (-40°F - 140°F)
5% - 100% (includes condensing)
40.6°C (105°F) maximum
Maximum power rating
36 000 VA
27