Chapter 7. PDU specifications

When the PDU is connected to a dedicated power source, it conforms to UL60950,
CSA C22.2-60950, EN-60950, and IEC-60950 standards. The following table
contains the product specifications for the PDUs. The PDUs in the following list
correspond by number to the rated voltages, maximum power ratings, and power
cords that are listed in the table:
10. DPI 60 amp/208 V 3-phase Enterprise C19 PDU with IEC 309 3P+Gnd
© Copyright IBM Corp. 2006
1. DPI 32 amp/250 V 1-phase Enterprise C13 PDU with IEC 309 2P+N+Gnd
connector
2. DPI 60 amp/208 V 1-phase Enterprise C13 PDU with IEC 309 2P+Gnd
connector
3. DPI 63 amp/250 V 1-phase Enterprise C13 PDU with IEC 309 2P+N+Gnd
connector
4. DPI 32 amp/250 V 3-phase Enterprise C13 PDU with IEC 309 3P+N+Gnd
connector
5. DPI 30 amp/208 V 1-phase Enterprise C13 PDU with Nema L6-30P connector
6. DPI 60 amp/208 V 3-phase Enterprise C13 PDU with IEC 309 3P+Gnd
connector
7. DPI 60 amp/208 V 1-phase Enterprise C19 PDU with IEC 309 2P+Gnd
connector
8. DPI 63 amp/250 V 1-phase Enterprise C19 PDU with IEC 309 2P+N+Gnd
connector
9. DPI 32 amp/250 V 3-phase Enterprise C19 PDU with IEC 309 3P+N+Gnd
connector
connector
Height
Width
Depth
Additional Clearance
Weight (not including line cord)
Weight of line cord (approximate,
varies by model of PDU)
Operating temperature at 0-914 m
(0-3000 ft) (room ambient)
Operating temperature at 914-2133 m
(3000-7000 ft) (room ambient)
Operating humidity
Localized air temperature in PDU
43.9 mm (1.73 in.)
447 mm (17.6 in.)
350 mm (13.78 in.)
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
6.3 kg (13.8 lb)
5.4 kg (11.8 lb)
10°- 35°C (50°- 95°F)
10°- 32°C (50°- 90°F)
8-80% (noncondensing)
60°C (140°F) maximum