Certification
Test
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
IEC 60255-5
IEEE 1613 Type Tests
NOTE
• If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (during disturbance, errors
may occur but recovery is automatic).
• If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (during disturbance, no
errors will occur).
ESD
Radiated RFI
Fast Transient
Oscillatory
44
Description
Voltage Dips
DC Power ports
& Interrupts
AC Power ports
Damped Oscillatory
DC Power ports
AC Power ports
Mains Frequency
Voltage
DC Power ports
Ripple on DC
DC Power ports
Power Supply
Dielectric Strength
DC Power ports
AC Power ports
HV Impulse
DC Power ports
AC Power ports
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
30% for 0.1 s, 60% for 0.1 s, 100% for 0.05 s
30% for 1 period, 60% for 50 periods
100% for 5 periods, 100% for 50 periods
Signal ports
2.5 kV common, 1 kV differential mode @ 1MHz
2.5 kV common, 1 kV differential mode @ 1MHz
2.5 kV common, 1 kV differential mode @ 1MHz
Signal ports
30 V Continuous, 300 V for 1 s
30 V Continuous, 300 V for 1 s
Signal ports
Signal ports
2.5 kV common & differential mode @ 1MHz
2.5 kV common & differential mode @ 1MHz
Test Levels
10%
2 kV  (Fail-Safe Relay output)
1.5 kV
2 kV
5 kV (Fail-Safe Relay output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV common mode @ 1MHz
EMC and Environmental Type Tests
RUGGEDCOM RS969
Installation Guide
Severity
Levels
2
3
3
3
4
4
3