Models FDCA401HEN, 401HES

165
60
50
237
Required space for maintenance and air flow
L2
Air
inlet
L1
(
Maintenance
space
40
99
Terminal block
55
50
15
920
Holes for anchor bolt
(M10×4 pcs.)
580
175
50
15
Holes for drain
295
(ø20×3 pcs.)
Air inlet
L3
L4
)
Air outlet
Liquid piping: ø9.52 (3/8")
(Flare connecting)
Gas piping: ø15.88 (5/8")
(Flare connecting)
Liquid piping: ø9.52 (3/8")
(Flare connecting)
Gas piping: ø15.88 (5/8")
(Flare connecting)
Opening for
electric wring
Opening for
electric wring
Opening for piping
and electric wring
Opening for piping
and electric wring
Opening for piping
and electric wring
Minimum allowable space to the obstacles
Installation
Mark
L1
L2
L3
L4
Notes
(1) It is prohibited to install in a space enclosed with walls
at four sides.
(2) Unit must be secured with anchor bolts.
Anchor bolt should not protrude more than 15 mm above
the surface.
(3) Where strong winds blow, the blow outlet must be
oriented at right angle against the wind direction.
(4) Secure a space of 1 m or more above the unit.
(5) Barrier standing in front of the blow outlet must be lower
than the height of unit.
35
-
-
Opening for piping
50
and electric wring
27
50
Opening for electric wiring
40
VIEW A
15
50
Unit:mm
1
2
type
Open
Open
300
5
Open
150
300
5
5
Unit: mm
A
3
500
150
5