(2) Correction of cooling and heating capacity in relation to air flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low
(3) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Models FDCA301~601
(1)
Equivalent piping length
m
Heating
FDCA301 model
FDCA401 model
Cooling
FDCA501 model
FDCA601 model
Models FDCA801, 1001
Equivalent piping length
(1)
m
Heating
FDCA801 model
Cooling
FDCA1001 model
Note
(1) Calculate the equivalent length using the following formula.
However, install the piping so that the equivalent length is within +5 m of the piping distance limit )actual length) for each respective piping system.
• Equivalent Length = Actual Length + (equivalent length of bends x number of bends in the piping)