7. If needed, repeat step "3" on page 79 through step "6" on page 79 to replace the other secondary
expander module.
8. Replace the top cover, as described in "Installing or replacing the top cover: 2145-92F " on page 72.
9. If needed, reconnect the power cables to the expansion enclosure, as described in "Powering on the
5U expansion enclosure: 2145-92F " on page 126.
10. Check the LEDs on the top of the secondary expander module to verify that it is receiving power.
" SAN Volume Controller 2145-92F expansion enclosure LEDs and indicators" on page 130 describes
the status indicated by the LEDs.

Installing or replacing the fascia: 2145-92F

During the initial installation process or after you perform service, you can install the fascia components
on the front of a 2145-92F expansion enclosure.
About this task
The 4U fascia covers the display panel of the expansion enclosure. It is attached to the enclosure by four
screws. The bottom 1U fascia covers both of the power supply units (PSUs) on the enclosure. As Figure
90 on page 80 shows, the fascias are independent; you can remove or replace one without having to
remove or replace the other.
Figure 90. Fascia components on the expansion enclosure
Note: When the expansion enclosure is shipped, the 4U and 1U fascia are not installed. You must install
them as part of the initial installation process.
Procedure
Attach the front (4U) fascia
1. Align the front 4U fascia with the enclosure so that the thumbscrews go through the holes on each
side. As Figure 91 on page 81 shows, this action aligns the screw holes on the back of the fascia with
the screw holes on the front flange of the enclosure.
80 SAN Volume Controller : Model 2145-SV1 Hardware Installation Guide