Wiring and Setting Up the System
Setting Address of Panel Bus I/O Modules
During CARE engineering, each Panel Bus I/O module is
assigned its own unique address. For the sake of clarity for
maintenance personnel, it is recommended that you
address the Panel Bus I/O modules in ascending order
0 through F.
Hex switch
0
1
Address
01
02
Hex switch
8
9
Address
09
10
Table 24 HEX switch settings and addresses
Use the rotary HEX switch to set the address to the one
►
already defined during CARE engineering.
LOCK
Fig. 38
HEX switch location
Notes
If the HEX switch is changed, the Panel Bus I/O module
will revert to its default configuration.
With L
W
Bus I/O modules, the HEX switch is
ON
ORKS
without function.
EN1B-0375GE51 R0910
2
3
4
5
6
03
04
05
06
07
A
B
C
D
E
11
12
13
14
15
4
4
Setting I/O Bus Switch
Set the I/O Bus switch S2 of the XCL8010 Controller
►
Module depending on the modules connected to
terminals 71 ... 78 and the desired communication as
follows:
Communication
7
L
W
Bus
ON
ORKS
08
only
F
Panel Bus and
L
W
Bus
ON
ORKS
16
Table 25 I/O Bus switch settings
Fig. 39
S2 I/O Bus switch
28
S2 setting
Terminals
LON
71 ... 74 L
ON
75 ... 78 L
ON
11 ... 14 L
ON
Panel
71 ... 74 Panel Bus
75 ... 78 Panel Bus
11 ... 14 L
ON
Excel 800
W
Bus
ORKS
W
Bus
ORKS
W
Bus
ORKS
W
Bus
ORKS