Wiring And Setting Up The System; General Safety Considerations; Wiring Terminals - Honeywell Excel 800 SYSTEM Installation And Commissioning Instructions

Table of Contents

Advertisement

Excel 800

Wiring and Setting Up the System

General Safety Considerations

 When connecting the XCL8010 Controller Module or
Excel 800 I/O modules, both VDE, National Electric Code
(NEC) or equivalent, and any local regulations con-
cerning grounding and zero voltage must be observed.
 Electrical work should be carried out by a qualified
electrician.
 The electrical connections must be made at the terminal
blocks. The corresponding connection diagrams are
located on the individual controller module and
I/O modules.
 For Europe only: To comply with CE requirements,
devices with a voltage in the range of 50 ... 1000 VAC or
75 ... 1500 VDC, which are not provided with a supply
cord and plug or with other means for disconnection from
the supply having a contact separation of at least 3 mm
in all poles, must have the means for disconnection
incorporated in the fixed wiring.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet.
Disconnect the power supply before making connections
to or removing connections from terminals of controller or
I/O modules.
Do not use spare terminals as wiring support points.
Do not reconnect the power supply until you have
completed the installation.
Observe precautions for handling electrostatic sensitive
devices.

Wiring Terminals

Wiring Push-In Terminals
The terminal sockets of the pluggable I/O modules are
available in versions (XS821-22, XS823, and XS824-25)
featuring convenient push-in terminals for easy wiring. Of
the mixed I/O modules, the XF830A likewise features push-
in terminals.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
Solid conductor H05/07) V-U
Stranded conductor H05(07) V-K
Stranded conductor with wire end
ferrules (without plastic collar)
Stripping length
Table 22 Push-in terminals wiring specifications
Wiring Screw-Type Terminals
The terminal sockets of the pluggable I/O modules are
available in versions (XSU821-22, XSU823, and XSU824-
25) featuring screw-type terminals. The mixed I/O modules
are likewise available in a version (the XFU830A) featuring
screw-type terminals.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
Solid conductor H05/07) V-U
Stranded conductor H05(07) V-K
Stranded conductor with wire end
ferrules (without plastic collar)
Stripping length
Table 23 Screw-type terminals wiring specifications
23
Wiring and Setting Up the System
0.14 ... 1.50 mm
0.25 ... 1.50 mm
0.25 ... 1.50 mm
0.25 ... 1.50 mm
8.0 +1.0 mm
0.14 ... 1.50 mm
0.25 ... 1.50 mm
0.25 ... 1.50 mm
0.25 ... 1.50 mm
11.0 +1.0 mm
EN1B-0375GE51 R0910
2
2
2
2
2
2
2
2