Description of the I/O Modules
Manual Override in the AUTO Position
When a manual override of the ... R 824 Relay Output
Module is set to the "AUTO" position, and the corresponding
relay output has been configured, the following applies:
If the L
W
network is functioning properly, the
ON
ORKS
logical status of the relay output will be "AUTO."
If the L
W
network is not functioning properly, the
ON
ORKS
feedback signal will be switched to the safety position
value.
The feedback signal on the L
nvoDoActPosnFb[ ] will have a value of either 0% or
100%, and a state of -1.
The status LED (yellow) will indicate the actual logical
state of the relay output as commanded (by
nviDoSwitch[ ]).
When a manual override of the ... R 824 Relay Output
Module is set to the "AUTO" position, and the corresponding
relay output has not been configured, the following applies:
Regardless as to whether the L
functioning properly or not, values from the L
Bus will be ignored, and there will be no heartbeat or
safety position.
The feedback signal on the L
nvoDoActPosnFb[ ] will have a value of 0% and a state
of 0.
The status LED will be unlit.
EN1B-0375GE51 R0910
W
network:
ON
ORKS
W
network is
ON
ORKS
W
ON
ORKS
W
network:
ON
ORKS
Manual Override in the ON Position
When a manual override of the ... R 824 Relay Output
Module is set to the "ON" position, the following applies:
If the relay output has been configured, its logical state
will depend upon the actual output configuration.
If the relay output is unconfigured, it will be switched ON.
Regardless of configuration, the feedback signal on the
L
W
network: nvoDoActPosnFb[ ] will have a
ON
ORKS
value of 1000...0% and a state of -1.
Regardless of configuration, the status LED (yellow) will
flash to indicate "manual override."
Manual Override in the OFF Position
When a manual override of the ... R 824 Relay Output
Module is set to the "OFF" position, the following applies:
If the relay output has been configured, its logical state
will depend upon the actual output configuration.
If the relay output is unconfigured, it will be switched
OFF.
Regardless of configuration, the feedback signal on the
L
W
network: nvoDoActPosnFb[ ] will have a
ON
ORKS
value of 0% (direct) or 100% (reverse) and a state of -1.
Regardless of configuration, the status LED (yellow) will
flash to indicate "manual override."
Note
Panel Bus I/O modules feature watchdog functionality. Con-
sequently, if the module's firmware stops running (due, e.g.,
to updating), the watchdog will switch OFF the module's
outputs – even if the corresponding manual overrides (if
present) have been set to ON. Thus, the manual overrides
should NOT be thought of as emergency overrides; rather,
they are subordinate to the given Panel Bus I/O module's
processor and firmware.