LION System

Setting Address of Panel Bus I/O Modules

During engineering, each Panel Bus I/O module is assigned
its own unique address. For the sake of clarity for
maintenance personnel, it is recommended that you
address the Panel Bus I/O modules in ascending order
0 through F.
Hex switch
0
1
Address
01
02
Hex switch
8
9
Address
09
10
Table 24 HEX switch settings and addresses
Use the rotary HEX switch to set the address to the one
already defined using the engineering tool.
LOCK
Fig. 37
HEX switch location
NOTE:
If the HEX switch is changed, the Panel Bus I/O
module will revert to its default configuration.
NOTE:
With L
W
Bus I/O modules, the HEX
ON
ORKS
switch is without function.
2
3
4
5
6
7
03
04
05
06
07
08
A
B
C
D
E
F
11
12
13
14
15
16
4
4

Setting I/O Bus Switch

Set the I/O Bus switch S2 of the CLLIONLC01 depending
on the modules connected to terminals 71 ... 78 and the
desired communication as follows:
Communication
L
W
Bus
ON
ORKS
only
Panel Bus and
L
W
Bus
ON
ORKS
Table 25 I/O Bus switch settings
S2
Panel
LO N
I/O Bus
Fig. 38
S2 I/O Bus switch
27
Wiring and Setting Up the System
S2 setting
Terminals
LON
71 ... 74 L
W
ON
75 ... 78 L
W
ON
11 ... 14 L
W
ON
Panel
71 ... 74 Panel Bus
75 ... 78 Panel Bus
11 ... 14 L
W
ON
EN1Z-0921GE51 R0315
Bus
ORKS
Bus