Wiring and Setting Up the System

Wiring and Setting Up the System

General Safety Considerations

 When connecting the CLLIONLC01 or LION I/O modules,
both VDE, National Electric Code (NEC) or equivalent,
and any local regulations concerning grounding and zero
voltage must be observed.
 Electrical work should be carried out by a qualified
electrician.
 The electrical connections must be made at the terminal
blocks. The corresponding connection diagrams are
located on the individual controller module and
I/O modules.
 For Europe only: To comply with CE requirements,
devices with a voltage in the range of 50 ... 1000 VAC or
75 ... 1500 VDC, which are not provided with a supply
cord and plug or with other means for disconnection from
the supply having a contact separation of at least 3 mm
in all poles, must have the means for disconnection
incorporated in the fixed wiring.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet.
Disconnect the power supply before making connections
to or removing connections from terminals of controller or
I/O modules.
Do not use spare terminals as wiring support points.
Do not reconnect the power supply until you have
completed the installation.
Unused terminals must be closed (by completely
screwing in the terminal screws), thus preventing the
accidental touching of "live" parts.
Observe precautions for handling electrostatic sensitive
devices.
EN1Z-0921GE51 R0315

Wiring Push-in Terminals

The terminal sockets of the pluggable I/O modules are
available in versions (XS821-22, XS823, and XS824-25)
featuring convenient push-in terminals for easy wiring. The
CLIOP830A likewise features push-in terminals.
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
Solid conductor H05/07) V-U
Stranded conductor H05(07) V-K
Stranded conductor with wire end
ferrules (without plastic collar)
Stripping length
Table 22 Push-in terminals wiring specifications
NOTE:
In the case of solid conductors, the use of
ferrules is prohibited.
NOTE:
Use only one conductor per push-in terminal.
NOTE:
If two stranded wires are to be connected to a
single push-in terminal, twin wire end ferrules
must be used.
Wiring Screw-Type Terminals
The terminal sockets of the pluggable I/O modules are also
available with screw-type terminals (XSU821-22, XSU823,
and XSU824-25).
For correct wiring, cables must fulfill the following
specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge
Solid conductor H05/07) V-U
Stranded conductor H05(07) V-K
Stranded conductor with wire end
ferrules (without plastic collar)
Stripping length
Table 23 Screw-type terminals wiring specifications
22
LION System
2
0.14 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
8.0 +1.0 mm
2
0.14 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
2
0.25 ... 1.50 mm
11.0 +1.0 mm