Table 24 - Electrical data - WKD/WKH Compressor motor and condenser motor
Compressor
Number
Type
Model
Rated Amps (1)
Locked rotor Amps (2)
Outdoor Fan
Nominal Airflow
Type
Diameter
Drive type
Number
Motor HP
Motor Rated Amps (1)
Motor Locked rotor Amps (2)
Motor RPM
(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor
Table 25 - Electrical data - TKD/TKH Supply fan motor
Indoor Fan
Nominal Airflow
Static pressure available (4)
Maximum static pressure available (5)
Type
Diameter / Width
Drive type
Number
Motor HP (Standard/Oversized)
Motor Rated Amps (Standard/Oversized)
Motor Locked rotor Amps (Standard/Oversized) (A)
Motor RPM (Standard/Oversized)
(4) At the nominal airflow with standard drive
(5) At the nominal airflow with oversized drive when available
RT-SVX19A-E4
Installation
(A)
(A)
(m
3
/h)
(mm)
(kW)
(A)
(A)
(rpm)
YKD/H
155
(m
3
/h)
8500
(Pa)
150
(Pa)
350
FC Centrifugal
(in / in)
15" / 15"
Belt
#
1
(kW)
2.2 / 3.0
(A)
4.6 / 6.5
36.4 / 57
(rpm)
1450 / 2870
WKD/H
WKD/H
125
155
2
2
Scroll
Scroll
6T / 6T
7 .5T /7 .5T
10.0 / 10.0
12.1 / 12.1
74 / 74
79 / 79
15300
15850
Axial
Axial
660
660
Direct
Direct
2
2
0.25
0.25
1.6
1.6
3.8
3.8
925
925
YKD/H
YKD/H
175
9850
11210
75
375
FC Centrifugal
FC Centrifugal
15" / 15"
18" / 18"
Belt
1
3.0 / 4.6
3.0 / 4.6
6.5 / 9.0
6.5 / 9.0
57 / 71.9
57 / 71.9
2870 / 2900
2870 / 2900
WKD/H
200
2
Scroll
10T / 10T
17 .5 / 17 .5
98 / 98
23600
Axial
710
Direct
2
0.56
2.3
5.8
950
YKD/H
200
250
14100
175
75
450
375
FC Centrifugal
18" / 18"
Belt
Belt
1
1
4.6 / -
9 / -
71.9 / -
2900 / -
29