Trane RT-SVX19A-E4 Installation Operation & Maintenance page 45

Rooftop units
Table of Contents

Advertisement

Thermostat signals are as follows:
R 24VAC power to thermostat
Y1 Call for compressor 1 or first
stage cooling
Y2 Call for compressor 2 or 2nd
stage cooling
G Call for supply fan
W1 Call for heat 1
W2 Call for heat 2
Heat pump only:
X2 Call for emergency heat
O Switchover valve On = cooling,
Off = heating
T Bias for heat anticipation for those
mechanical thermostats that use
this function
RT-SVX19A-E4
Operation
Conventional thermostat –
Gas/ Electric, Electric Heat:
Function when
Input/connection
energized :
G (fan)
Fan runs continuously
except during
unoccupied mode
(see next page)
Y1 (compressor 1
Compressor #1 runs
or economizer)
or economizer
operates
Y2 (compressor 2
Compressor #2 also
or compressor 1
runs, or #1
while economizing)
compressor runs
while economizing
W1 (gas / electric
1st stage heat
heat first stage)
W2 (gas / electric
2nd stage heat (if
heat 2nd stage)
available)
Conventional thermostat –
Heat Pump
Function when
Input/connection
energized
Cooling mode:
G (fan)
Fan runs continuously
except during
unoccupied mode
(see next page)
O (reversing valve
Reversing valve in
during cooling)
cool mode
Y1 + O
Compressor #1 runs
(first stage cooling)
or economizer
operates
Y1 + Y2 + O
Compressor #2 also
(2nd stage cool)
runs, or #1
compressor runs
while economizing.
Heating mode:
G (fan)
Fan runs continuously
except during
unoccupied mode
(see below)
Y1 (both
Both compressors
compressors 1st
run
stage heat)
Y2 (during heating
No change
– nothing happens)
W2 (electric heat
2nd stage (electric)
2nd stage)
heat
X2 (electric heat
Electric heat only –
only)
no compressors
T (provides heat anticipation signal for
those mechanical thermostats that use this
feature. If the thermostat used does not
have a "T" terminal, disregard this
terminal.
45