Trane RT-SVX19A-E4 Installation Operation & Maintenance page 35

Rooftop units
Table of Contents

Advertisement

RT-SVX19A-E4
Controls
Mounting the duct-mounted CO
sensor
1. Select a proper location on the
duct to mount the CO
2. Drill a 22-25 mm hole in the
mounting surface for sensor
insertion (Figure 13).
3. Attach the mounting plate to the
duct wall with four screws.
4. Insert the sensor through the
mounting plate, adjusting the
depth for optimal air sensing.
Figure 13 - Duct-mounted CO
5
1
/
in. ( 42 mm)
8
7
/
in. (2 2 mm)
8
Figure 14 - Duct-mounted CO
1
2
/
in. (64 mm)
3
2
CO
sensor maintenance
2
2
This CO
2
stability and requires no
sensor.
2
maintenance. In most environments
the recommended calibration
interval is five years. A trained
service technician can use a
portable CO
calibration. If, when checking the
sensor, the reading differs too much
from the reference value, the sensor
can be recalibrated in the field. A
calibration kit, software, and
calibration gases are required. If
certified accuracy is required, the
sensor must be calibrated against
accurate and traceable calibration
gases in a laboratory. Consult Trane
BAS for further details.
sensor
2
5
1
/
in.
8
(42 mm)
insertion depth
2
1
1
/
- 5
/
in. (80 - 140 mm )
8
2
sensor has excellent
meter to certify sensor
2
35