Table PD-9 — Gross Cooling Capacities (MBh) TTA125B Condensing Unit with TWE100B Air Handler
Enter.
Dry
CFM
Bulb
61
Airflow
(°F)
TGC
SHC TGC SHC TGC SHC
75
109.9
81.1 121.9 71.0 135.2 49.8
3025
80
110.2
92.5 122.2 78.4 135.2 63.2
85
110.6 104.2 122.5 90.4 135.4 75.2
90
113.5 113.5 122.7 101.8 135.7 87.3
75
112.6
84.5 124.7 68.5 138.0 50.8
3350
80
112.8
96.8 125.0 81.5 138.0 65.0
85
113.6 109.5 125.1 94.2 138.3 78.0
90
117.6 117.6 125.5 106.7 138.6 91.1
75
114.6
87.3 127.0 70.4 140.3 51.8
3675
80
115.1 100.8 127.3 84.5 140.3 66.6
85
116.3 114.6 127.5 97.9 140.6 80.7
90
121.3 121.3 127.9 111.3 141.0 94.7
75
116.6
90.2 129.0 72.3 142.3 52.7
4000
80
117.1 104.5 129.4 87.2 142.3 68.2
85
118.5 118.5 129.6 101.4 142.7 83.2
90
124.5 124.5 130.0 115.8 143.1 98.1
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-9 — Gross Cooling Capacities (kW) TTA125B Condensing Unit with TWE100B Air Handler
Enter.
Dry
3
m
/h
Bulb
16.1
Airflow
(°C)
TGC
SHC TGC SHC TGC SHC
24
32.2
23.7 35.7 20.8 39.6 14.6
5139
27
32.3
27.1 35.8 23.0 39.6 18.5
29
32.4
30.5 35.9 26.5 39.6 22.0
32
33.2
33.2 35.9 29.8 39.7 25.5
24
33.0
24.7 36.5 20.1 40.4 14.9
5692
27
33.0
28.3 36.6 23.9 40.4 19.0
29
33.3
32.1 36.6 27.6 40.5 22.8
32
34.4
34.4 36.8 31.2 40.6 26.7
24
33.6
25.6 37.2 20.6 41.1 15.2
6244
27
33.7
29.5 37.3 24.7 41.1 19.5
29
34.0
33.6 37.3 28.7 41.2 23.6
32
35.5
35.5 37.5 32.6 41.3 27.7
24
34.1
26.4 37.8 21.2 41.7 15.4
6796
27
34.3
30.6 37.9 25.5 41.7 20.0
29
34.7
34.7 38.0 29.7 41.8 24.3
32
36.5
36.5 38.1 33.9 41.9 28.7
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
22
Performance
Data
85
67
73
61
TGC
SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
106.3
79.2 117.8 69.3 130.6 48.0 102.0 76.9 113.3 67.5 125.5 46.3 97.6 74.6 108.5 65.5 120.2 44.3
106.5
90.6 118.1 76.5 130.6 61.3 102.5 88.4 113.7 74.5 125.6 59.3 98.1 86.1 108.9 72.3 120.2 57.1
107.1 102.3 118.2 88.3 130.8 73.3 103.3 100.2 113.8 86.1 125.9 71.3 99.2 98.0 109.1 83.8 120.6 69.2
110.5 110.5 118.6 99.8 131.1 85.4 107.3 107.3 114.2 97.7 126.2 83.3 103.6 103.6 109.5 95.4 120.9 81.2
108.5
82.3 120.4 66.6 133.2 49.1 104.3 80.0 115.7 64.5 127.9 47.2 99.8 77.7 110.7 62.3 122.3 45.3
109.0
94.7 120.7 79.6 133.2 63.0 104.8 92.5 116.1 77.5 128.0 61.0 100.3 90.1 111.1 75.3 122.4 58.8
110.0 107.6 120.8 92.1 133.5 76.1 106.1 105.5 116.3 90.0 128.3 74.1 101.8 101.8 111.4 87.6 122.8 71.9
114.5 114.5 121.3 104.6 133.8 89.1 111.0 111.0 116.7 102.5 128.7 87.1 107.2 107.2 111.8 100.1 123.2 84.9
110.7
85.3 122.5 68.5 135.3 50.0 106.4 83.0 117.7 66.4 129.9 48.2 101.6 80.6 112.5 64.1 124.1 46.2
111.2
98.7 122.9 82.5 135.4 64.7 106.9 96.4 118.1 80.4 130.0 62.6 102.1 94.0 113.0 78.1 124.3 60.4
112.2 112.2 123.1 95.8 135.7 78.7 108.7 108.7 118.4 93.6 130.4 76.6 104.8 104.8 113.3 91.2 124.7 74.5
117.9 117.9 123.5 109.2 136.1 92.7 114.3 114.3 118.8 107.0 130.5 90.3 110.4 110.4 113.8 104.7 124.9 87.9
112.5
88.1 124.4 70.3 137.1 51.0 108.1 85.8 119.4 68.1 131.5 49.1 103.2 83.3 114.1 65.9 125.6 46.9
113.0 102.4 124.8 85.2 137.3 66.2 108.6 100.2 119.6 82.7 131.8 64.1 103.9 97.7 114.4 80.3 125.9 61.9
115.1 115.1 125.1 99.3 137.7 81.2 111.5 111.5 120.2 97.0 132.2 79.1 107.5 107.5 114.9 94.6 126.4 76.9
121.1 121.1 125.5 113.7 137.8 95.7 117.3 117.3 120.7 111.4 132.4 93.5 113.2 113.2 115.6 109.1 126.6 91.1
29.4
19.4
22.8
16.1
TGC
SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
31.1
23.2 34.5 20.3 38.2 14.1 29.9 22.5 33.2 19.8 36.8 13.6 28.6 21.8 31.8 19.2 35.2 13.0
31.2
26.5 34.6 22.4 38.2 17.9 30.0 25.9 33.3 21.8 36.8 17.4 28.7 25.2 31.9 21.2 35.2 16.7
31.4
29.9 34.6 25.8 38.3 21.5 30.2 29.3 33.3 25.2 36.9 20.9 29.0 28.7 31.9 24.6 35.3 20.3
32.4
32.4 34.7 29.2 38.4 25.0 31.4 31.4 33.5 28.6 36.9 24.4 30.3 30.3 32.1 27.9 35.4 23.8
31.8
24.1 35.2 19.5 39.0 14.4 30.5 23.4 33.9 18.9 37.5 13.8 29.2 22.7 32.4 18.2 35.8 13.3
31.9
27.7 35.3 23.3 39.0 18.5 30.7 27.1 34.0 22.7 37.5 17.9 29.4 26.4 32.5 22.1 35.9 17.2
32.2
31.5 35.4 27.0 39.1 22.3 31.1 30.9 34.0 26.3 37.6 21.7 29.8 29.8 32.6 25.7 36.0 21.1
33.5
33.5 35.5 30.6 39.2 26.1 32.5 32.5 34.2 30.0 37.7 25.5 31.4 31.4 32.7 29.3 36.1 24.9
32.4
25.0 35.9 20.0 39.6 14.7 31.1 24.3 34.5 19.4 38.0 14.1 29.8 23.6 32.9 18.8 36.3 13.5
32.5
28.9 36.0 24.1 39.6 18.9 31.3 28.2 34.6 23.5 38.1 18.3 29.9 27.5 33.1 22.9 36.4 17.7
32.8
32.8 36.0 28.0 39.7 23.0 31.8 31.8 34.7 27.4 38.2 22.4 30.7 30.7 33.2 26.7 36.5 21.8
34.5
34.5 36.2 32.0 39.8 27.1 33.5 33.5 34.8 31.3 38.2 26.4 32.3 32.3 33.3 30.7 36.6 25.7
32.9
25.8 36.4 20.6 40.2 14.9 31.7 25.1 35.0 19.9 38.5 14.4 30.2 24.4 33.4 19.3 36.8 13.7
33.1
30.0 36.5 25.0 40.2 19.4 31.8 29.3 35.0 24.2 38.6 18.8 30.4 28.6 33.5 23.5 36.9 18.1
33.7
33.7 36.6 29.1 40.3 23.8 32.6 32.6 35.2 28.4 38.7 23.2 31.5 31.5 33.7 27.7 37.0 22.5
35.4
35.4 36.7 33.3 40.3 28.0 34.3 34.3 35.3 32.6 38.8 27.4 33.1 33.1 33.9 31.9 37.1 26.7
Ambient Temperature (°F)
95
Entering Wet Bulb (°F)
67
73
61
Ambient Temperature (°C)
35.0
Entering Wet Bulb (°C)
19.4
22.8
16.1
19.4
System
(I-P)
105
115
67
73
61
(SI)
40.6
46.1
22.8
16.1
19.4
67
73
22.8
SS-PRC003-EN