Trane SS-PRC003-EN Owner's Manual page 17

Split system cooling units
Table of Contents

Advertisement

Table PD-4 — Gross Cooling Capacities (MBh) TTA085A Condensing Unit with TWE100A Air Handler
Enter.
Dry
CFM
Bulb
61
Airflow
(°F)
TGC
SHC TGC SHC TGC SHC
75
87.7
68.7 97.0 57.2 107.1 39.2
2500
80
88.0
80.1 97.3 66.3 107.2 51.4
85
89.8
89.8 97.5 77.6 107.6 63.2
90
94.4
94.4 97.9 89.0 107.8 74.9
75
89.6
72.2 99.1 56.7 109.0 40.0
2800
80
90.2
84.8 99.4 69.7 109.3 53.3
85
93.1
93.1 99.5 81.9 109.6 66.3
90
98.0
98.0 100.2 94.6 109.7 78.8
75
91.2
75.5 100.7 58.8 110.5 40.8
3100
80
92.1
89.4 100.9 72.5 111.0 55.1
85
96.1
96.1 101.2 86.1 111.3 69.2
90
101.1 101.1 102.3 100.0 111.5 82.7
75
92.6
78.7 102.1 60.8 111.8 41.5
3400
80
93.9
93.8 102.3 75.4 112.4 56.8
85
98.6
98.6 102.7 90.1 112.8 72.0
90
103.8 103.8 103.9 103.9 112.9 86.4
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
Table PD-4 — Gross Cooling Capacities (kW) TTA085A Condensing Unit with TWE100A Air Handler
Enter.
Dry
3
m
/h
Bulb
16.1
Airflow
(°C)
TGC
SHC TGC SHC TGC SHC
24
25.7
20.1 28.4 16.7 31.4 11.5
4248
27
25.8
23.4 28.5 19.4 31.4 15.1
29
26.3
26.3 28.5 22.7 31.5 18.5
32
27.6
27.6 28.7 26.1 31.6 21.9
24
26.2
21.1 29.0 16.6 31.9 11.7
4757
27
26.4
24.8 29.1 20.4 32.0 15.6
29
27.3
27.3 29.1 24.0 32.1 19.4
32
28.7
28.7 29.3 27.7 32.1 23.1
24
26.7
22.1 29.5 17.2 32.4 12.0
5267
27
27.0
26.2 29.5 21.2 32.5 16.1
29
28.1
28.1 29.6 25.2 32.6 20.3
32
29.6
29.6 30.0 29.3 32.6 24.2
24
27.1
23.1 29.9 17.8 32.7 12.1
5777
27
27.5
27.5 30.0 22.1 32.9 16.6
29
28.9
28.9 30.1 26.4 33.0 21.1
32
30.4
30.4 30.4 30.4 33.1 25.3
Equal TGC and SHC values constitute dry coil conditions. Total Gross Cooling (TGC) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total
capacity.
All capacities shown are gross and have not considered indoor fan heat.
To obtain net cooling capacities subtract indoor fan heat.
TGC = Total Gross Cooling Capacity
SHC = Sensible Heat Capacity
SS-PRC003-EN
Performance
Data
85
67
73
61
TGC
SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
84.5
67.1 93.5 55.8 103.1 37.9 81.1 65.4 89.8 54.3 98.9 36.4 77.6 63.7 86.0 52.7 94.6 35.0
84.9
78.5 93.8 64.8 103.4 49.9 81.6 76.9 90.1 63.2 99.3 48.4 78.2 75.1 86.1 61.3 95.1 46.9
87.2
87.2 94.0 76.0 103.7 61.7 84.4 84.4 90.3 74.3 99.7 60.2 81.5 81.5 86.5 72.7 95.5 58.7
91.7
91.7 94.4 87.4 103.9 73.5 88.9 88.9 90.9 85.8 99.8 71.6 85.9 85.9 87.3 84.2 95.6 70.0
86.3
70.6 95.4 55.2 104.9 38.6 82.8 68.9 91.6 53.6 100.5 37.2 79.2 67.1 87.6 52.0 96.0 35.6
87.0
83.2 95.5 67.8 105.3 51.8 83.7 81.6 91.7 66.2 101.1 50.3 80.2 79.9 87.8 64.4 96.7 48.7
90.4
90.4 95.9 80.3 105.6 64.8 87.4 87.4 92.1 78.6 101.5 63.3 84.4 84.4 88.2 76.9 97.1 61.7
95.1
95.1 96.7 93.0 105.7 77.2 92.1 92.1 93.1 91.4 101.6 75.6 89.0 89.0 89.1 89.1 97.3 73.9
87.8
73.9 96.9 57.3 106.2 39.4 84.2 72.1 93.0 55.7 101.8 37.9 80.5 70.3 88.9 54.1 97.2 36.3
88.9
87.8 97.1 70.8 106.8 53.6 85.2 85.2 93.2 69.1 102.5 52.1 82.1 82.1 89.2 67.4 98.1 50.5
93.1
93.1 97.5 84.5 107.2 67.7 90.1 90.1 93.7 82.8 102.9 66.2 86.9 86.9 89.7 81.1 98.3 64.1
98.1
98.1 98.8 98.5 107.4 81.1 94.9 94.9 95.0 95.0 103.1 79.5 91.6 91.6 91.7 91.7 98.7 77.8
89.1
77.0 98.2 59.2 107.4 40.0 85.5 75.3 94.2 57.6 102.9 38.4 81.7 73.5 90.0 56.0 98.2 36.8
90.5
90.5 98.5 73.7 108.1 55.3 87.4 87.4 94.5 72.0 103.7 53.8 84.1 84.1 90.3 70.2 99.2 52.2
95.6
95.6 99.0 88.5 108.3 70.1 92.4 92.4 95.0 86.8 104.0 68.5 89.0 89.0 91.0 85.1 99.4 66.7
100.7 100.7 100.8 100.8 108.7 84.8 97.4 97.4 97.5 97.5 104.4 83.2 94.0 94.0 94.0 94.0 99.9 81.4
29.4
19.4
22.8
16.1
TGC
SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC TGC SHC
24.7
19.6 27.4 16.3 30.2 11.1 23.7 19.2 26.3 15.9 29.0 10.7 22.7 18.6 25.2 15.4 27.7 10.2
24.9
23.0 27.5 19.0 30.3 14.6 23.9 22.5 26.4 18.5 29.1 14.2 22.9 22.0 25.2 18.0 27.9 13.7
25.5
25.5 27.5 22.2 30.4 18.1 24.7 24.7 26.4 21.8 29.2 17.6 23.9 23.9 25.3 21.3 28.0 17.2
26.8
26.8 27.7 25.6 30.4 21.5 26.0 26.0 26.6 25.1 29.2 21.0 25.1 25.1 25.6 24.7 28.0 20.5
25.3
20.7 27.9 16.2 30.7 11.3 24.2 20.2 26.8 15.7 29.4 10.9 23.2 19.6 25.6 15.2 28.1 10.4
25.5
24.4 28.0 19.9 30.8 15.2 24.5 23.9 26.9 19.4 29.6 14.7 23.5 23.4 25.7 18.9 28.3 14.3
26.5
26.5 28.1 23.5 30.9 19.0 25.6 25.6 27.0 23.0 29.7 18.5 24.7 24.7 25.8 22.5 28.4 18.1
27.9
27.9 28.3 27.2 31.0 22.6 27.0 27.0 27.3 26.8 29.8 22.1 26.1 26.1 26.1 26.1 28.5 21.7
25.7
21.6 28.4 16.8 31.1 11.5 24.7 21.1 27.2 16.3 29.8 11.1 23.6 20.6 26.0 15.8 28.5 10.6
26.0
25.7 28.4 20.7 31.3 15.7 25.0 25.0 27.3 20.2 30.0 15.2 24.0 24.0 26.1 19.7 28.7 14.8
27.3
27.3 28.5 24.7 31.4 19.8 26.4 26.4 27.4 24.2 30.1 19.4 25.4 25.4 26.3 23.7 28.8 18.8
28.7
28.7 28.9 28.8 31.4 23.7 27.8 27.8 27.8 27.8 30.2 23.3 26.8 26.8 26.9 26.9 28.9 22.8
26.1
22.6 28.8 17.3 31.5 11.7 25.0 22.0 27.6 16.9 30.1 11.2 23.9 21.5 26.4 16.4 28.8 10.8
26.5
26.5 28.8 21.6 31.7 16.2 25.6 25.6 27.7 21.1 30.4 15.7 24.6 24.6 26.4 20.6 29.0 15.3
28.0
28.0 29.0 25.9 31.7 20.5 27.0 27.0 27.8 25.4 30.4 20.0 26.1 26.1 26.6 24.9 29.1 19.5
29.5
29.5 29.5 29.5 31.8 24.8 28.5 28.5 28.6 28.6 30.6 24.4 27.5 27.5 27.5 27.5 29.2 23.8
Ambient Temperature (°F)
95
Entering Wet Bulb (°F)
67
73
61
Ambient Temperature (°C)
35.0
40.6
Entering Wet Bulb (°C)
19.4
22.8
16.1
19.4
System
(I-P)
105
115
67
73
61
(SI)
46.1
22.8
16.1
19.4
67
73
22.8