These factory-mounted motors are wired for a 460V power supply. Refer to the wiring diagram inside the motor terminal box when reconnecting the motor leads for a
208 or 230 volt power supply.
TABLE 7 - ELECTRICAL DATA
Blower
Power
Motor
Supply
HP
208-3-60
1-1/2
230-3-60
460-3-60
208-3-60
2
230-3-60
460-3-60
NOTE: Refer to Form 035-16602-002 for electrical data on units equipped with an electric
heat accessory.
1
Dual element, time delay fuses.
2
Based on three 60°C, 14 AWG, insulated copper conductors in steel conduit, a 3% voltage
drop.
Unitary Products Group
Accessory
2400
10 KW
0.01
16 KW
0.01
26 KW
0.03
36 KW
0.05
0.03
0.02
3200
10 KW
0.02
16 KW
0.03
26 KW
0.06
36 KW
0.09
0.05
0.05
Adjustable Motor Pulley
Blower RPM
Pitch Dia.
(Inches)
1-1/2
655 - 880
2.8 - 3.8
2
700 - 950
Max. Fuse
Max. Wire
1
FLA
Size,
Length
AMPS
FCHP090
5.3
10
5.8
10
2.7
5
FDHP120
7.5
10
6.8
10
3.4
5
(To be included with Duct System Static Resistance)
Static Resistance, IWG
2700
0.01
0.02
0.04
0.07
0.03
0.03
3600
0.02
0.04
0.07
0.11
0.06
0.06
Fixed Blower Pulley
Bore
Pitch Dia.
(Inches)
(Inches)
7/8
2
(Ft.)
Wire Size
#19 Solid
207
#18 Solid
209
#18 Stranded
897
#16 Stranded
#14 Stranded
146
#12 Stranded
178
To determine the total circuit length, add the following distances: