13.3 PCCC

Ethernet-enabled Allen-Bradley legacy PLCs (such as the PLC5E and SLC-
5/05 series) use a protocol called PCCC (Programmable Controller
Communication Commands) to communicate over the Ethernet network. The
interface card supports PCCC for direct connectivity to these PLCs.
If a connection timeout or socket-level error occurs, the driver will trigger a
timeout event as described in section 10.7.4.

13.3.1 Tag Reference

Register contents are read from and written to the interface card via PCCC by
reference to an integer "file/section number" and an "offset/element" within that
file. Reading is performed via the PCCC "PLC5 Read" (DF1 protocol typed
read) service, and writing is performed via the PCCC "PLC5 Write" (DF1
protocol typed write) service.
The formula to calculate which register is targeted in the interface card is
provided in Equation 3.
target
register
In Equation 3, "target register" ∈[1...1485], "file number" ∈[10...24] (which
means N10...N24), and "offset" is restricted only by the limitations of the
programming software (but is a value of 1485 max). Table 5 provides some
examples of various combinations of file/section numbers and offsets/elements
which can be used to access drive registers. Note that there are multiple
different combinations of file/section numbers and offsets/elements that will
result in the same drive register being accessed.
File/Section
Number
N10
N12
N11
N20
N24
N10
In addition to providing access to the drive registers in their "standard"
numerical locations as mentioned above, the registers can also be accessed in
a special "assembly object" type format by targeting integer file N50. What this
means is that when N50 is targeted for reading, what is actually returned by the
interface card is the user-defined register data as ordered by the EtherNet/IP
produced register configuration array (refer to section 10.8.4). Similarly, when
(
=
file
number
Table 5: PCCC Target Register Examples
Offset/Element
)
×
+
-
10
100
offset
1
99
199
7
85
1485
85
Equation 3
Start Target
Register
1
299
299
1007
1485
1485