Input Delay; Output Delay - Siemens SIMATIC S5 Manual

Ip 265 high speed sub control
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

General Operation
4.2.2

Input delay

The input delay of the 24 V inputs consists of two times:
Delay of the input circuit:
Debouncing time:
Remember:
For adaptation to simple sensors, the fast 24 V inputs can be debounced. You can configure the
debouncing time with the aid of COM 265.
4.2.3

Output delay

The output delay of the 24 V outputs is determined by the output wiring.
Delay of the output wiring:
The following table gives an overview of possible output delays depending on the ohmic load of the
24 V output wiring.
Ohmic load
15 mA
*
50 mA
*
500 mA
*
*
Peak value (not an r.m.s specification)
4-6
Table 4-2. Delays of the 24 V Outputs
Delays
Rising Edge
typ. 10 µs
typ. 10 µs
typ. 10 µs
typ. 15 µs
1 to 2 ms
typ. 70 µs (500 mA ohmic load)
Falling Edge
typ. 150 µs
typ. 90 µs
typ. 70 µs
IP 265
Output Frequency
max. 1 kHz
max. 2 kHz
max. 4 kHz