IP 265
Set/Reset operations (S/R..)
Set/Reset operation
Set/Reset operation for latching signal output
(reset dominant) "S":
The language element has one Set input (S), one
Reset input (R) and one output (Q). The Reset input
is dominant.
Example:
If inputs I 0.0 and I 0.1 are both "1", the
operation is reset dominant. Output
Q 0.5 is "0".
Set/Reset operation for latching signal output
(set dominant) "R":
The language element has one Set input (S), one
Reset input (R) and one output (Q). The Set input is
dominant.
Example:
If inputs I 0.0 and I 0.1 are both "1", the
operation is set dominant. Output Q 0.5
is "1".
Note
The Set/Reset operations are not assigned a flag number in the IP 265 user program.
Possible options for Set/Reset operations:
Each input can be inverted.
Outputs can be inverted when the output of the relevant language element leads immediately to
the output bar of the control system flowchart.
Each of the two Set/Reset operations can be converted into its opposite operation or into a
binary logic operation.
EWA 4NEB 812 6130-02a
Table 9-3. "Set/Reset operations"
Programming the IP 265 with COM 265
CSF (example)
I 0.0
S
I 0.1
R
Q
I 0.1
R
I 0.0
S
Q
Q 0.5
Q 0.5
9-13